-
48
-
'14 • SR-T-157
(10) Outline of cooling operation
(a) Operation of major functional components in Cooling mode
(b) Detail of control in each mode (Pattern)
(i) Fuzzy operation
During the fuzzy operation, the air flow and the compressor speed are controlled by calculating the difference be
-
tween the indoor temperature setting correction temperature and the retum air temperature.
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON
ON
OFF
Thermostat ON
Thermostat OFF
Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
20~110rps
20~110rps
20~74rps
20~44rps
SRR35ZJ-S
20~74rps
20~74rps
20~55rps
20~34rps
SRR25ZJ-S
Model
Fan speed
Auto
MED
HI
LO
(11) Outline of dry (dehumidifying) operationion
(a) Purpose of DRY mode
The purpose is "Dehumidification", and not to control the humidity to the target condition.
Indoor/outdoor unit control the operation condition to reduce the humidity, and also prevent over cooling.
(b) Outline of control
(i)
Indoor unit fan speed and compressor are controlled by the area which is selected by the temperature difference.
(ii)
The indoor unit check the current area by every 5 minutes, and operate by the next checking.
(c) Other
When the outside temperature and room temperature is low for cooling operation, indoor unit can not operate in cooling,
and dehumidify. In this case, the units operate in heating to rise the room temperature, and after that start DRY operation.
Indoor unit fan speed
Area
D
C
B
A
Me speed
Indoor unit
fan speed
ULo(Lo) speed
STOP
Limited
䋨
Lower than
normal cooling operation
䋩
Compressor
Limited
speed
Minimum
䋨
Lower than the speed in ”Area A”
䋩
STOP
set temperature
Difference between set temperature and return temperature