(iii) Ending condition
1) If one of following conditions is met during the hot start control, this control is terminated, and the fan is operated with
the set airflow volume.
a) Heat exchanger thermistor (ThI-R1 or R2, whichever higher) detects 35°C or higher.
b) It has elapsed 7 minutes after starting the hot start control.
(g) Hot keep
Hot keep control is performed at the start of the defrost control.
(i)
Control
1) When the indoor heat exchanger temperature (detected with Th
I
-R1 or R2) drops to 35°C or lower, the speed of
indoor fan is changed to the lower tap at each setting.
2) During the hot keep, the louver horizontal control signal is transmitted.
(ii)
Ending condition
When the indoor fan is at the lower tap at each setting, it returns to the set airflow volume as the indoor heat exchanger
temperature rises to 45°C or higher.
(h) Thermostat operation
(i) Cooling
1) Thermostat is operated with the room temperature control.
2) Thermostat is turned ON or OFF relative to the set room temperature as shown below.
3) Thermostat is turned ON when the room temperature is in the range of -1 < Set point < +1 at the start of cooling opera-
tion (including from heating to cooling).
(ii) Heating
1)
Thermostat is operated with the room temperature control.
2) Thermostat is turned ON or OFF relative to the set room temperature as shown below.
3) Thermostat is turned ON when the room temperature is in the range of -1 < Set point < +1 at the start of cooling opera-
tion (including from cooling to heating).
(iii) Fan control during heating thermostat OFF
1) Following fan controls during the heating thermostat OFF can be selected with the indoor function setting of the wired
remote control.
①
Low
fan speed
(Factory default),
②
Set fan speed,
③
Intermittence,
④
Fan OFF
2)
When the “Low fan speed (Factory default)” is selected, the following taps are used for the indoor fans.
・ For DC motor : ULo tap
3)
When the “Set fan speed” is selected, it is operated with the set fan speed also in the thermostat OFF condition.
Thermostat OFF
Set room temperature
Temperature drop
Temperature rise
-1
+1
Thermostat ON
Thermostat OFF
Heater OFF
Temperature rise
Temperature drop
Thermostat ON
Set room temperature
-1
+1
-1
+1
Heater ON