66
-
'14 • SR-T-157
(v) External input/output control (CnT)
Be sure to connect the wired remote control to the indoor unit. Without wired remote control remote operation by CnT is not
possible to perform.
①
Operation output
(CnT-2: XR1)
②
Heating output
(CnT-3: XR2)
③
Thermostat ON output
(CnT-4: XR3)
④
Error output
(CnT-5: XR4)
⑤
Remote operation input
(CnT-6: No-voltage contactor)
XR1
1
2
3
4
5
6
XR3
XR4
CnT
Blue
12V
XR2
Option
XR5
(i) Output for external control (remote display)
Following output connectors (CnT) are provided on the indoor control PCB for monitoring operation status.
①
Operation output:
Outputs DC12V signal for driving relay during operation
②
Heating output:
Outputs DC12V signal for driving relay during heating operation
③
Thermostat ON output:
Outputs DC12V signal for driving relay when compressor is operating.
④
Error output:
Outputs DC12V signal for driving relay when anomalous condition occurs.
(ii) Remote operation input
Remote operation input connector (CnT-6) is provided on the indoor control PCB.
However remote operation by CnT-6 is not effective, when “Center mode” is selected by center control.
In case of plural unit (twin, triple, double twin), remote operation input to CnT-6 on the slave indoor unit is invalid.
Only the “LEVEL INPUT” is acceptable for external input
, however when the indoor function setting of “Level
input (Factory default)” or “Pulse input” is selected by the function for “External input” of the wired remote control,
operation status will be changed as follows.
1) In case of “Level input” setting (Factory default)
Input signal to CnT-6 is OFF→ON …… unit ON
Input signal to CnT-6 is ON→OFF …… unit OFF
Operation is not inverted.
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
CnT-6 input
Unit A
Unit B
Note: The latest operation has priority
It is available to operate/stop by remote control or center control
2) In case of “Pulse input” setting (Local setting)
It is effective only when the input signal to CnT-6 is changed OFF→ON, and at that time unit operation [ON/OFF] is
inverted.
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
CnT-6 input
Unit A
Unit B