'15 • SR-T-185
'09•SRK-DB-087D
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
(3) Correction relative to frosting on outdoor heat exchanger during heating
How to obtain the cooling and heating capacity
=
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
30
0.935
1.0
Air inlet temperature of
outdoor unit in °C WB
Adjustment coefficient
-15
0.95
0.95
0.94
0.93
0.91
0.88
0.86
0.87
0.92
1.00
-10
-9
-7
-5
-3
-1
1
3
5 or more
ZM-S
ZM-S
R
R