background image

-

 

 

-

 '15 • SR-T-185

INSTALLATION MANUAL FOR OUTDOOR UNIT

RWC012A044A

SRC20·25·35·50

Model DXC06·09·12·18

Accessories for outdoor unit

• Model name and power source

• Refrigerant piping length

• Piping, wiring and miscellaneous small parts

• Indoor unit installation manual

Necessary tools for the installation work

Wrench key (Hexagon) [4m/m]
Vacuum pump
Vacuum pump adapter (Anti-reverse flow type)
(Designed specifically for R410A)
Gauge manifold (Designed specifically for R410A)
Charge hose (Designed specifically for R410A)
Flaring tool set (Designed specifically for R410A)
Gas leak detector (Designed specifically for R410A)
Gauge for projection adjustment
(Used when flare is made by using conventional flare tool)

9

10

11

12
13
14
15

16

Plus headed driver
Knife
Saw
Tape measure
Hammer
Spanner wrench
Torque wrench [14.0

~

62.0N·m (1.4

~

6.2kgf·m)]

Hole core drill (65mm in diameter)

1
2
3
4
5
6
7
8

Grommet
(Heat pump
type only)

SRC20~35

Model

DXC06~12

Model SRC50/DXC18

Q’ty

1

4

1

Option parts

Sealing plate
Sleeve
Inclination plate
Putty
Drain hose (extension hose)
Piping cover
(for insulation of connection piping)

Q’ty

1
1
1
1
1

1

1

Drain elbow (Heat pump type only)

Check before installation work

a
b
c
d
e

f

2

R410A REFRIGERANT USED

1. HAULAGE AND INSTALLATION

(Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)

Intake

The height of a wall is 1200mm or less.

(

service

space

)

Intake

Outlet

Fasten with bolts

(M10-12)

Use a thicker block to anchor deeper.

Use a long block to extend the width.

CAUTION

When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity center position.

If not properly balanced, the unit can be thrown off-balance and fall.

1) Delivery

2) Portage

3) Selecting the installation location

5) Installation space

L

3

L

2

L

4

L

1

Model SRC20~50/DXC06~18

Model SRC20~35/DXC06~12

Example installation

Size

L1
L2
L3
L4

Open

100
100
250

280

75
80

Open

280

Open

80

250

180

Open

80

Open

(mm)

I

II

III

IV

6) Installation

Pad

Over 500mm

Intake

Outlet

31

2.

5

24

.3

14

.8

29

0

111.6

510

158.4

35

1.

6

Model SRC50/DXC18

Intake

Outlet

31

2.

5

24

.3

14

.8

29

0

89

510

201

35

1.

6

• Deliver the unit as close as possible to the installation site before removing it from

the packaging.

• When you have to unpack the unit for a compelling reason before you haul it to

the installation point, hoist the unit with nylon slings or ropes and protection pads

so that you may not damage the unit.

• The right hand side of the unit as viewed from the front (diffuser side) is heavier.

A person carrying the right hand side must take heed of this fact. A person

carrying the left hand side must hold with his right hand the handle provided on

the front panel of the unit and with his left hand the corner column section.

(1) If the unit is installed in the area where the snow will accumulate, following measures are required.

The bottom plate of unit and intake, outlet may be blocked by snow.

1 Install the unit on the base so that the bottom is

higher than snow cover surface.

Since drain water generated by defrost control may freeze, following measures are required.

• Do not execute drain piping work by using a drain elbow and drain grommets (accessories).

[Refer to Drain piping work.]

Determine refrigerant pipe size pursuant to the following guidelines based on

the indoor unit specifications.

Without nitrogen gas, a large quantity of foreign matters

(oxidized film) are created, causing a critical failure from

capillary tube or expansion valve clogging.

2 Install the unit under or provide the roof on site.

Be careful of the following conditions and choose an installation place.
• Where air is not trapped.

• Where the installation fittings can be firmly installed.

• Where wind does not hinder the intake and outlet pipes.

• Out of the heat range of other heat sources.

• A place where stringent regulation of electric noises is not applicable.

• Where it is safe for the drain water to be discharged.

• Where noise and hot air will not bother neighboring residents.

• Where snow will not accumulate.

• Where strong winds will not blow against the outlet pipe.

• A place where no TV set or radio receiver is placed within 1m.

(If electrical interference is caused, seek a place less likely to cause the problem)

• If a operation is conducted when the outdoor air temperature is –5 C lower, the outdoor unit should be

installed at a place where it is not influenced by natural wind.

• Where it is likely that the unit is subjected to strong winds, provide wind guards according to the

following guidelines. Strong winds can cause performance degradation, an accidental stop due to a rise of

high pressure and a broken fan.

Do not install the unit in places which exposed to sea breeze (e.g. coastal area) or calcium chloride (e.g.

snow melting agent), exposed to ammonia substance (e.g. organic fertilizer).

2. REFRIGERANT PIPING WORK

1) Restrictions on unit installation and use

2) Determination of pipe size

15m or less

10m or less

10m or less

L

H

H

L

H

Outdoor unit

Indoor unit

The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below.

Restrictions

Model SRC20~35/DXC06~12

Marks appearing in the

drawing on the right

Main pipe length

When the outdoor unit is positioned higher,

When the outdoor unit is positioned lower,

Elevation difference between

indoor and outdoor units

Plug the end of the pipe with tape, or other

material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

<N2>

Ni

tro

ge

n

Brazing

Station valve

Primary side

Secondary side

0.5MPa

Hand

Relief valve

Nitrogen

gas

Brazing must be performed under a nitrogen gas flow.

About brazing

When pipe is brazing.

4) Caution about selection of installation location

• Walls surrounding the unit in the four sides are not

acceptable.

• There must be a 1-meter or larger space in the above.

• When more than one unit are installed side by side,

provide a 250mm or wider interval between them as a

service space. In order to facilitate servicing of

controllers, please provide a sufficient space between

units so that their top plates can be removed easily.

• Where a danger of short-circuiting exists, install guide

louvers.

• When more than one unit are installed, provide sufficient

intake space consciously so that short-circuiting may not

occur.

• Where piling snow can bury the outdoor unit, provide

proper snow guards.

• In installing the unit, fix the unit’s legs with bolts specified on the above.

• The protrusion of an anchor bolt on the front side must be kept within 15mm.

• Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

• Refer to the above illustrations for information regarding concrete foundations.

• Install the unit in a level area. (With a gradient of 5mm or less.) Improper installation can result in a

compressor failure, broken piping within the unit and abnormal noise generation.

1 Anchor bolt fixed position

2 Notabilia for installation

(2) If the unit can be affected by strong wind, following measures are required.

Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger

anomalous stop of the unit due to rising of high pressure.

1 Place the unit outlet side is turned to the wall.

2 Install so the direction of the air from the

blowing outlet will be perpendicular to the

direction of the wind.

• Check the following points in light of the indoor unit specifications and the installation site.

• Observe the following restrictions on unit installation and use. Improper installation can result in a compressor failure or performance degradation.

• Additional refrigerant charge is not required at all (Model SRC20~35/DXC06~12).

25m or less

15m or less

15m or less

Dimensional restrictions

Model SRC50/DXC18

ø12.7

Flare

ø12.7

ø12.7

Gas pipe

ø6.35

Flare

ø6.35

ø6.35

Model SRC50/DXC18

Liquid pipe

ø9.52

Flare

ø9.52

ø9.52

Gas pipe

ø6.35

Flare

ø6.35

ø6.35

Model SRC20~35/DXC06~12

Liquid pipe

Outdoor unit connected

Refrigerant piping (branch pipe L)

Indoor unit connected

Notabilia as a unit designed for R410A

• Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant.

A cylinder containing R410A has a pink indication mark on the top.

• A unit designed for R410A has adopted a different size indoor unit servic valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.

The processed dimension of the flared part of a refrigerant pipe and a flare nut’s parallel side measurement have also been altered to raise strength against pressure.

Accordingly, you are required to arrange dedicated R410A tools listed in the table on the left before installing or servicing this unit.

• Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.

• In charging refrigerant, always take it out from a cylinder in the liquid phase.

• All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)

CAUTION

• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in order

to protect yourself.

• The precautionary items mentioned below are distinguished into two levels,

and

.

: Wrong installation would cause serious consequences such as injuries or death.
: Wrong installation might cause serious consequences depending on circumstances.

Both mentions the important items to protect your health and safety so strictly follow them by any means.

• Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the

operating methods as well as the maintenance methods of this equipment to the user according to the owner’s
manual.

• Keep the installation manual together with owner’s manual at a place where any user can read at any time.

Moreover if necessary, ask to hand them to a new user.

• For installing qualified personnel, take precautions in respect to themselves by using suitable protective

clothing, groves, etc., and then perform the installation works.

• Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
• If unusual noise can be heard during operation, consult the dealer.
• The meanings of “Marks” used here are shown as follows:

• This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to page 20.
• When install the unit, be sure to check whether the selection of installation place, power source specifications, usage limitation (piping length, height differences between indoor and outdoor units, power

source voltage and etc.) and installation spaces.

SAFETY PRECAUTIONS

WARNING

Never do it under any circumstances.

Always do it according to the instruction.

CAUTION

WARNING

CAUTION

WARNING

CAUTION

• Carry out the electrical work for ground lead with care.

Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.

• Installation must be carried out by the qualified installer.

If you install the system by yourself, it may cause serious trouble such as water leaks,

electric shocks, fire and personal injury, as a result of a system malfunction. Do not

carry out the installation and maintenance work except the by qualified installer.

• Install the system in full accordance with the installation manual.

Incorrect installation may cause bursts, personal injury, water leaks, electric

shocks and fire.

• Be sure to use only for household and residence.

If this appliance is installed in inferior environment such as machine shop and etc.,

it can cause malfunction.

• When installing in small rooms, take prevention measures not to

exceed the density limit of refrigerant in the event of leakage, referred

by the formula (accordance with ISO5149).

If the density of refrigerant exceeds the limit, please consult the dealer and install

the ventilation system, otherwise lack of oxygen can occur, which can cause serious

accident.

• Use the original accessories and the specified components for

installation.

If parts other than those prescribed by us are used, It may cause water leaks,

electric shocks, fire and personal injury.

• Install the unit in a location with good support.

Unsuitable installation locations can cause the unit to fall and cause material

damage and personal injury.

• Ensure the unit is stable when installed, so that it can withstand

earthquakes and strong winds.

Unsuitable installation locations can cause the unit to fall and cause material

damage and personal injury.

• Ventilate the working area well in the event of refrigerant leakage during

installation.

If the refrigerant comes into contact with naked flames, poisonous gas is produced.

• Use the prescribed pipes, flare nuts and tools for R410A.

Using existing parts (for R22 or R407C) can cause the unit failure and serious

accidents due to burst of the refrigerant circuit.

• Tighten the flare nut by torque wrench with specified method.

If the flare nut were tightened with excess torque, this may cause burst and

refrigerant leakage after a long period.

• Do not open the service valves for liquid line and gas line until

completed refrigerant piping work, air tightness test and evacuation.

If the compressor is operated in state of opening service valves before completed

connection of refrigerant piping work, air can be sucked into refrigerant circuit,

which can cause bust or personal injury due to anomalously high pressure in the

refrigerant.

• The electrical installation must be carried out by the qualified electrician

in accordance with “the norm for electrical work” and “national wiring

regulation”, and the system must be connected to the dedicated circuit.

Power source with insufficient capacity and incorrect function done by improper

work can cause electric shocks and fire.

• Be sure to shut off the power before starting electrical work.

Failure to shut off the power can cause electric shocks, unit failure or incorrect

function of equipment.

• Be sure to use the cables conformed to safety standard and cable

ampacity for power distribution work.

Unconformable cables can cause electric leak, anomalous heat production or fire.

• This appliance must be connected to main power source by means of a

circuit breaker or switch (fuse:16A) with a contact separation of at least

3mm.

• Arrange the wiring in the control box so that it cannot be pushed up

further into the box. Install the service panel correctly.

Incorrect installation may result in overheating and fire.

• Use the prescribed cables for electrical connection, tighten the cables

securely in terminal block and relieve the cables correctly to prevent

overloading the terminal blocks.

Loose connections or cable mountings can cause anomalous heat production or fire.

• Be sure to fix up the service panels.

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.

• Be sure to switch off the power source in the event of installation,

inspection or servicing.

If the power source is not shut off, there is a risk of electric shocks, unit failure or

personal injury due to the unexpected start of fan.

• Stop the compressor before removing the pipe after shutting the

operation valve on pump down work.

If the pipe is removed when the compressor is in operation with the service valve

open, air would be mixed in the refrigeration circuit and it could cause explosion

and injuries due to abnormal high pressure in the cooling cycle.

• Only use prescribed option parts. The installation must be carried out

by the qualified installer.

If you install the system by yourself, it can cause serious trouble such as water

leaks, electric shocks, fire.

• Be sure to wear protective goggles and gloves while at work.

• Earth leakage breaker must be installed.

If the earth leakage breaker is not installed, it can cause electric shocks.

• Ensure that no air enters in the refrigerant circuit when the unit is

installed and removed.

If air enters in the refrigerant circuit, the pressure in the refrigerant circuit

becomes too high, which can cause burst and personal injury.

• Do not processing, splice the power cord, or share a socket with other power plugs.

This may cause fire or electric shock due to defecting contact, defecting insulation

and over-current etc.

• Do not bundling, winding or processing for the power cable. Or, do not

deforming the power plug due to tread it.

This may cause fire or heating.

• Do not run the unit with removed panels or protections.

Touching rotating equipments, hot surfaces or high voltage parts can cause

personal injury due to entrapment, burn or electric shocks.

• Do not perform any change of protective device itself or its setup

condition.

The forced operation by short-circuiting protective device of pressure switch and

temperature controller or the use of non specified component can cause fire or

burst.

• Use the circuit breaker for all pole correct capacity. Circuit breaker

should be the one that disconnect all poles under over current.

Using the incorrect circuit breaker, it can cause the unit malfunction and fire.

• Install isolator or disconnect switch on the power source wiring in

accordance with the local codes and regulations.

The isolator should be locked in OFF state in accordance with EN60204-1.

• After maintenance, all wiring, wiring ties and the like, should be returned

to their original state and wiring route, and the necessary clearance from

all metal parts should be secured.

• Secure a space for installation, inspection and maintenance specified in

the manual.

Insufficient space can result in accident such as personal injury due to falling from

the installation place.

• Take care when carrying the unit by hand.

If the unit weights more than 20kg, it must be carried by two or more persons. Do

not carry by the plastic straps, always use the carry handle when carrying the unit

by hand. Use gloves to minimize the risk of cuts by the aluminum fins.

• Dispose of any packing materials correctly.

Any remaining packing materials can cause personal injury as it contains nails and

wood. And to avoid danger of suffocation, be sure to keep the plastic wrapper

away from children and to dispose after tear it up.

• Be sure to insulate the refrigerant pipes so as not to condense the

ambient air moisture on them.

Insufficient insulation can cause condensation, which can lead to moisture

damage on the ceiling, floor, furniture and any other valuables.

• When perform the air conditioner operation (cooling or drying operation)

in which ventilator is installed in the room. In this case, using the air

conditioner in parallel with the ventilator, there is the possibility that

drain water may backflow in accordance with the room lapse into the

negative pressure status. Therefore, set up the opening port such as

incorporate the air into the room that may appropriate to ventilation (For

example; Open the door a little). In addition, just as above, so set up the

opening port if the room lapse into negative pressure status due to

register of the wind for the high rise apartment etc.

• Do not install the unit in the locations listed below.

•Locations where carbon fiber, metal powder or any powder is floating.

•Locations where any substances that can affect the unit such as sulphide gas,

chloride gas, acid and alkaline can occur.

•Vehicles and ships.

•Locations where cosmetic or special sprays are often used.

•Locations with direct exposure of oil mist and steam such as kitchen and

machine plant.

•Locations where any machines which generate high frequency harmonics are

used.

•Locations with salty atmospheres such as coastlines.

•Locations with heavy snow (If installed, be sure to provide base flame and snow

hood mentioned in the manual).

•Locations where the unit is exposed to chimney smoke.

•Locations at high altitude (more than 1000m high).

•Locations with ammonic atmospheres (e.g. organic fertilizer).

•Locations with calcium chloride (e.g. snow melting agent).

•Locations where heat radiation from other heat source can affect the unit.

•Locations without good air circulation.

•Locations with any obstacles which can prevent inlet and outlet air of the unit.

•Locations where short circuit of air can occur (in case of multiple units

installation).

•Locations where strong air blows against the air outlet of outdoor unit.

•Locations where something located above the unit could fall.

It can cause remarkable decrease in performance, corrosion and damage of

components, malfunction and fire.

• Do not install the outdoor unit in the locations listed below.

Locations where discharged hot air or operating sound of the outdoor unit can

bother neighborhood.

Locations where outlet air of the outdoor unit blows directly to an animal or

plants. The outlet air can affect adversely to the plant etc.

Locations where vibration can be amplified and transmitted due to insufficient

strength of structure.

Locations where vibration and operation sound generated by the outdoor unit

can affect seriously (on the wall or at the place near bed room).

Locations where an equipment affected by high harmonics is placed (TV set or

radio receiver is placed within 1m).

Locations where drainage cannot run off safely.

It can affect surrounding environment and cause a claim.

• Do not install the unit near the location where leakage of combustible

gases can occur.

If leaked gases accumulate around the unit, it can cause fire.

• Do not install the unit where corrosive gas (such as sulfurous acid gas etc.)

or combustible gas (such as thinner and petroleum gases) can accumulate

or collect, or where volatile combustible substances are handled.

Corrosive gas can cause corrosion of heat exchanger, breakage of plastic parts

and etc. And combustible gas can cause fire.

• Do not install nor use the system close to the equipment that generates

electromagnetic fields or high frequency harmonics.

Equipment such as inverters, standby generators, medical high frequency

equipments and telecommunication equipments can affect the system, and cause

malfunctions and breakdowns. The system can also affect medical equipment and

telecommunication equipment, and obstruct its function or cause jamming.

Do not install the outdoor unit in a location where insects and small

animals can inhabit.

Insects and small animals can enter the electric parts and cause damage or fire.

Instruct the user to keep the surroundings clean.

Do not use the base flame for outdoor unit which is corroded or damaged

due to long periods of operation.

Using an old and damage base flame can cause the unit falling down and cause

personal injury.

Do not use any materials other than a fuse with the correct rating in the

location where fuses are to be used.

Connecting the circuit with copper wire or other metal thread can cause unit

failure and fire.

Do not touch any buttons with wet hands.

It can cause electric shocks.

Do not touch any refrigerant pipes with your hands when the system is in

operation.

During operation the refrigerant pipes become extremely hot or extremely cold

depending the operating condition, and it can cause burn injury or frost injury.

Do not touch the suction or aluminum fin on the outdoor unit.

This may cause injury.

Do not put anything on the outdoor unit and operating unit.

This may cause damage the objects or injury due to falling to the object.

Do not use the unit for special purposes such as storing foods, cooling

precision instruments and preservation of animals, plants or art.

Do not clean up the unit with water.

Over 500mm

Heavy

Wind

direction

Wind

direction

Summary of Contents for SRR25ZM-S

Page 1: ...TECHNICAL MANUAL ANUAL O g s32 4 INVERTER CEILING CONCEALED TYPE RESIDENTIAL AIR CONDITIONERS 3PLIT SYSTEM AIR TO AIR HEAT PUMP TYPE 322 3 322 3 TECHNICAL MANUAL updated April 10 2017 ...

Page 2: ...32 3ILENT MODE 33 PERATION CONTROL FUNCTION BY WIRELESS REMOTE CONTROL 4IMER OPERATION 3ELECTION OF THE ANNUAL COOLING FUNCTION 34 NSTALLING TWO AIR CONDITIONERS IN THE SAME ROOM 33 UTO RESTART FUNCTION 5NIT BUTTON 33 32 NSTALLATION OF INDOOR UNIT 20 NSTALLATION OF OUTDOOR UNIT 24 CONOMY OPERATION 34 IGH POWER OPERATION 34 IGHT SETBACK UTLINE OF HEATING OPERATION UTLINE OF DRY DEHUMIDIFYING OPRATI...

Page 3: ...roduct capacity Cooling capacity 2 5kW Model name SRR Ceiling concealed type SRC Outdoor unit M S 64 12 OPTION PARTS 87 13 TECHNICAL INFORMATION 64 78 1 Wired remote control 2 Interface kit SC BIKN E 3 Superlink E board SC ADNA E 82 5 Remote sensor kit SC THB E3 85 4 Bottom air inlet kit 6 Service mode Trouble mode access function 47 7 Inspection procedures corresponding to detail of trouble 55 45...

Page 4: ...ssible Air filter Quality Quantity Polypropylene net x 1 Shock vibration absorber Cushion rubber for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless remote control Room temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green ECONO Green Safety equipments Compressor overheat protection Overcurren...

Page 5: ...ir filter Quality Quantity Polypropylene net x 1 Shock vibration absorber Cushion rubber for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless remote control Room temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green ECONO Green Safety equipments Compressor overheat protection Overcurrent protec...

Page 6: ... C1 Drain piping D Hole for wiring E Suspension bolts M10 Symbol Content φ6 35 1 4 Flare φ9 52 3 8 Flare Drain piping C2 Gravity drainage VP25 I D 25 O D 32 Used with attached connector VP25 I D 25 O D 32 Used with attached connector φ25 x 2 Unit mm Wired remote control Option Wireless remote control Remote control signal receiver Remote control signal receiver Cord length 1 8m Notes 1 The model n...

Page 7: ...0 80 280 I I I 280 Open 80 75 Examplesof Dimensions installation I V 180 Open 80 Open Notes 1 It must not be surrounded by walls on the four sides 2 The unit must be fixed with anchor bolts An anchor bolt must not protrude more than 15mm 3 Where the unit is subject to strong winds lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction 4 Leave 1m or m...

Page 8: ... 15 SR T 185 3 Remote control Unit mm 60 26 167 a Wireless remote control ...

Page 9: ...ness 100 to 200m 0 5mm2 2 cores 0 75mm2 2 cores 1 25mm2 2 cores 2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cace Board Wiring Upper Lower Y X Tighten the screws after cutting off the thin part of screw mounting part Embedded mounting Pearl White Exterior appearance Munsell color N8 5 near equivalent Th...

Page 10: ... 15 SR T 185 Installation space R C cable 0 3mm2 2 core Adapted to RoHS directive Exterior appearance Munsell color Pearl White N8 5 near equivalent A PJZ000Z297 ii Model RC EX1A ...

Page 11: ...CNW DM DM F1 F 0 16A L 250V F2 F 3 15A L 250V Y BK RD CNS t t t 5 1 8 2 RD TB CNY Color Marks Blue Black BK Red BL RD White WH Yellow Y Color Mark Heat exchanger sensor Fan motor Room temp sensor Th1 Th21 2 Diode stack DS Fuse F1 2 Connector CNE FMI Terminal block TB Description Item Drain motor DM CNG CNS CNU CNW CNY DS Va Th1 Th2 1 Th2 2 FMI Yellow Green Y G Float switch FS Varistor Va INTERFACE...

Page 12: ...should be chosen along the regulations in each country The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country Model MAX running ...

Page 13: ...t Mike position Center Low points 4 NOISE LEVEL Model SRR25ZM S Sound pressure level 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB Standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 Mike position 1 5m Unit Air Condition ISO5151 T1 JIS C 9612 MODE Rated capacity value 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 ...

Page 14: ...ressure Level dB Standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 Condition ISO5151 T1 JIS C 9612 MODE Rated capacity value 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB Standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 1 5m 1m Unit Supply duct Return duct External staic pressure 10Pa Mike position 2m Air S...

Page 15: ... 1m Unit Mike position Center Low points Model SRR35ZM S Sound pressure level 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB Standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 Mike position 1 5m Unit Air Condition ISO5151 T1 JIS C 9612 MODE Rated capacity value 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Oct...

Page 16: ...ressure Level dB Standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 Condition ISO5151 T1 JIS C 9612 MODE Rated capacity value 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB Standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 1 5m 1m Unit Supply duct Return duct External staic pressure 10Pa Mike position 2m Air S...

Page 17: ...ice valve Heat exchanger Heat exchanger sensor Electronic expansion valve Liquid Strainer Receiver Muffler Capillary tube Outdoor air temp sensor Muffler Muffler Compressor Discharge pipe temp sensor Cooling cycle Heating cycle Check joint 4way valve Service valve Heat exchanger sensor Th3 TH3 Room temp sensor Th1 Th2 Gas TH2 Heat exchanger sensor TH1 EEV Capillary tube Heat exchanger 1 SRF series...

Page 18: ...ion Approximately 15 to 24 D B Refer to the selection chart Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows The net cooling and heating capacity can be obtained in the following way Net capacity Capacity shown on specification Correction factors as follows 1 Coefficient of cooling and heating capacity in relation to temperatures 0 6 0 7 0 8 0 9...

Page 19: ...ting on outdoor heat exchanger during heating How to obtain the cooling and heating capacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 30 0 935 1 0 Air inlet temperature of outdoor unit in CWB Adjustment coefficient 15 0 95 0 95 0 94 0 93 0 91 0 88 0 86 0 87 0 92 1 00 10 9 7 5 3 1 1 3 5 or more ZM S ZM S R R ...

Page 20: ...oor DB 23 DB 26 DB 27 DB 28 DB 31 DB 33 DB Outdoor air temp air temp WB 16 WB 18 WB 19 WB 20 WB 22 WB 24 WB Air flow 6 1 C H S C T C H S C T C H S C T C H S C T C H S C T C H S C T C H S C T DB 18 DB 20 DB 22 DB 24 DB 10 3 94 3 01 4 13 2 96 4 28 3 06 4 35 3 02 4 43 2 98 4 56 3 05 4 68 2 94 12 3 87 2 97 4 06 2 93 4 22 3 03 4 29 2 99 4 37 2 95 4 51 3 02 4 63 2 93 2 92 2 87 2 83 2 76 2 70 14 3 80 2 9...

Page 21: ...Locations where any substances that can affect the unit such as sulphide gas chloride gas acid and alkaline can occur Vehicles and ships Locations where cosmetic or special sprays are often used Locations with direct exposure of oil mist and steam such as kitchen and machine plant Locations where any machines which generate high frequency harmonics are used Locations with salty atmospheres such as...

Page 22: ...refrigerant gas pipe and refrigerant liquid pipe A 200 C 200 Air blowout direction Air outlet 100 450 B F E Screw CAUTION Completely seal the hole on the wall with putty Otherwise furniture or other may be wetted by leaked water or dewing putty putty Indoor side Outdoor side D D Grill Prepare on site 37 SELECTION OF INSTALLATION LOCATION INSTALLATION OF INDOOR UNIT Indoor unit Install at location ...

Page 23: ...ion drop Check if the water can flow out properly from both the drain outlet on the indoor unit and the end of the drain pipe after installation Insulating material to be removed Joint Rubber stopper to be removed Standard hard polyvinyl chloride pipe Connecting port of bottom drain pipes Outside diameter 25mm Connecting port of top drain pipe DRAIN PIPE 3 Make sure to make descending slope of gre...

Page 24: ... indication marks without fail Do not use new and old batteries together Disconnect When two air conditioners are installed in the same room use this setting when the two air conditioners are not operated with one wireless remote control Set the wireless remote control and indoor unit INSTALLING TWO AIR CONDITIONERS IN THE SAME ROOM Setting the wireless remote control Pull out the cover and take o...

Page 25: ... and strong winds Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury Ventilate the working area well in the event of refrigerant leakage during installation If the refrigerant comes into contact with naked flames poisonous gas is produced Use the prescribed pipes flare nuts and tools for R410A Using existing parts for R22 or R407C can cause t...

Page 26: ...w hood mentioned in the manual Locations where the unit is exposed to chimney smoke Locations at high altitude more than 1000m high Locations with ammonic atmospheres e g organic fertilizer Locations with calcium chloride e g snow melting agent Locations where heat radiation from other heat source can affect the unit Locations without good air circulation Locations with any obstacles which can pre...

Page 27: ...outlet pipe A place where no TV set or radio receiver is placed within 1m If electrical interference is caused seek a place less likely to cause the problem If a operation is conducted when the outdoor air temperature is 5 C lower the outdoor unit should be installed at a place where it is not influenced by natural wind Where it is likely that the unit is subjected to strong winds provide wind gua...

Page 28: ... 4 ø9 52 3 8 ø12 7 1 2 Recommended length of a tool handle mm Service valve size mm 5 Air tightness test Gas side service valve Do not hold the valve cap area with a spanner 3 Refrigerant pipe wall thickness and material NOTE Phosphorus deoxidized seamless copper pipe ICS 23 040 15 ICS 77 150 30 ø6 35 0 8 O type pipe ø9 52 0 8 O type pipe ø12 7 0 8 O type pipe Pipe diameter mm Minimum pipe wall th...

Page 29: ...valve Service valve Liquid side Service valve cap Service valve cap Service valve cap tightening torque N m Check joint blind nut tightening torque N m ø6 35 1 4 ø9 52 3 8 ø12 7 1 2 20 30 25 35 10 12 Service valve size mm Securely tighten the service valve cap and the check joint blind nut after adjustment 1 Dress refrigerant pipes both gas and liquid pipes for heat insulation and prevention of de...

Page 30: ... earth conductor yellow green Section of copper wire mm2 H05RNR4G1 5 Example or 245IEC57 Electrical installation work must be performed by an electrical installation service provider qualified by a power provider of the country Electrical installation work must be executed according to the technical standards and other regulations applicable to electrical installations in the country Do not use an...

Page 31: ...aring a common terminal number with an indoor outdoor connecting wire In cabling fasten cables securely with cable clamps so that no external force may work on terminal connections Grounding terminals are provided in the control box N L 1 2 N 3 1 2 N 3 Safety breaker 16A Earth leakage circuit breaker Earth Earth Power source Indoor unit Outdoor unit When wire length exceeds 30m use 2 5mm2 wires Mo...

Page 32: ...s for indoor and outdoor pipes have been insulated The reverse flow check cap is attached The cover of the pipe cover A faces downward to prevent rain from entering Gaps are properly sealed between the pipe covers A B and the wall surface pipes The screw of the side cover is tightened securely Switchgear or Circuit breaker capacity which is calculated from MAX over current should be chosen along t...

Page 33: ...button changes the air flow up down direction This switch is for setting the time This button selects SLEEP operation This switch selects the CLEAN operation This button selects ON TIMER operation This buttions is used for setting the cur rent time and timer function Switch for resetting microcomputer This button sets WEEKLY TIMER This button changes the HIGH POWER ECONOMY operation This buttion c...

Page 34: ...e J170 Illum TIMER light yellow Illuminates during TIMER operation Illum Unit ON OFF button Function Operation mode Indoor temperature setting Fan speed Flap Louver Timer switch COOL About 24ºC Auto Auto Continuous DRY About 25ºC HEAT About 26ºC When two air conditioners are installed in the room use setting when the two air conditioners are not operated with one wireless remote control Set the wi...

Page 35: ...nged When the NIGHT SETBACK botton is pressed When it has been 15 minutes since HIGH POWER operation has started e Not operable while the air conditioner is OFF f After HIGH POWER operation the sound of refrigerant flowing may be heard 6 High power operation Pressing the HI POWER ECONO button initiate a soft operation with the power suppressed in order to avoid an excessive cooling or heating The ...

Page 36: ...ng SRR25ZM S SRR35ZM S 4th speed 34 rps 4th speed 46 rps 5th speed 50 rps 4th speed 60 rps 11 Outline of heating operation a Operation of major functional components in heating mode ON OFF ON ON ON OFF few minutes ON ON ON HOT KEEP OFF OFF 3 minutes ON OFF OFF Thermostat ON Thermostat OFF Failure Heating Compressor Indoor fan motor Outdoor fan motor 4 way valve b Details of control at each operati...

Page 37: ...r unit during heating operation has counted 0 rps 10 times or more and all conditions of 1 2 3 and 5 above and the outdoor air temperature is 3 C or less are satisfied note that when the temperature for outdoor heat exchanger sensor TH2 is 5 C or less 62 rps or more 4 C or less less than 62 rps defrost operation is started ii Ending conditions Operation returns to the heating cycle when either one...

Page 38: ...RY mode The purpose is Dehumidification and not to control the humidity to the target condition Indoor outdoor unit control the operation condition to reduce the humidity and also prevent over cooling b Outline of control i Indoor unit fan speed and compressor are controlled by the area which is selected by the temperature difference ii The indoor unit check the current area by every 5 minutes and...

Page 39: ...d following the change of setting temperature with the remote control the hourly judgment of operation mode is cancelled If the setting temperature is changed with the wireless remote control the operation mode is judged immediately Signals of wireless remote control Display 6 5 4 3 2 1 0 1 2 3 4 5 6 Setting temperature Cooling 18 19 20 21 22 23 24 25 26 27 28 29 30 Dehumidifying 19 20 21 22 23 24...

Page 40: ...the compressor is stopped 3 When the outdoor heat exchanger temperature is in the range of 53 58 ºC if the compressor command speed is been maintained and the operation has continued for more than 30 seconds at the same speed it returns to the normal cooling operation c Cooling overload protective control i Operating conditions ii Detail of operation iii Reset conditions Item SRF25㨪50ZJX S Outdoor...

Page 41: ...ng conditions When the outdoor air temperature TH3 is 22ºC or higher continues for 30 seconds while the compressor command speed other than 0 rps i ii iii iv Taking the upper limit of compressor command speed range at 60 rps if the output speed obtained with the fuzzy calculation exceeds the upper limit the upper limit value is maintained The lower limit of compressor command speed is set to 40 rp...

Page 42: ...ounted on the discharge pipe Notes 1 When the discharge pipe temperature is in the range of 100 110ºC the speed is reduced by 4 rps 2 When the discharge pipe temperature is raised and continues operation for 20 seconds without changing then the speed is reduced again by 4 rps 3 If the discharge pipe temperature is in the range of 90 100ºC even when the compressor command speed is maintained for 3 ...

Page 43: ...nters first in the stop mode and then stops the entire system n Rotor lock If the motor for the compressor does not turn after it has been started it is determined that a compressor lock has occurred and the compressor is stopped o Outdoor fan motor protection If the outdoor fan motor has operated at 75 min 1 or under for more than 30 seconds the compressor and fan motor are stopped p Outdoor fan ...

Page 44: ... the flashing of display lights and the drain motor is turned ON The ON condition is maintained during the drain detection ii Heating 1 Operating conditions When the outdoor air temperature TH3 is 4ºC or lower continues for 30 seconds while the compressor command speed is other than 0 rps 2 Detail of operation The outdoor fan is stepped up by 2 speed step at each 20 seconds Upper limit 8th speed 3...

Page 45: ...OTING PROCEDURES FOR ELECTRICAL EQUIPMENT 1 Cautions 2 Items to check before troubleshooting 3 Troubleshooting procedure If the air conditioner does not run at all Important YES YES YES NO NO NO NO YES Reference Reference AC proced wireless source source satisfied ...

Page 46: ... 45 15 SR T 185 09 SRK DB 087D 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 46 47 53 47 53 s s ...

Page 47: ...put current value is found to be lower than the set value The air conditioner stops When the power transistor is judged breakdown while compressor starts The compressor is stopped Broken compressor wire Compressor blockage Trouble of outdoor unit When the value of the discharge pipe sensor exceeds the set value The air conditioner stops Gas shortage defective discharge pipe sensor service valve is...

Page 48: ...a are recorded for up to 5 previous occurrences Data which are older than the 5th previous occurrence are erased In addition data on the temperature of each sensor room temperature indoor heat exchanger outdoor heat exchanger outdoor air temperature discharge pipe remote control information operation switching fan speed switching are recorded when trouble occurs so more detailed information can be...

Page 49: ...Fan speed mode mode mode 21ºC 22ºC 23ºC 24ºC 25ºC 1 time previous previous time 2 times previous 3 times previous 4 times previous 5 times previous Only for indoor heat exchanger sensor 2 Indicates the number of occasions previous to the present the error display data are from Temperature setting 26ºC 27ºC 28ºC 29ºC 30ºC 1 time previous previous time 2 times previous 3 times previous 4 times previ...

Page 50: ...the stop stop code 2 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 3 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 4 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 5 times p...

Page 51: ...on of this anomalous temperature When the discharge pipe sensor s value exceeds the set value When the outdoor heat exchanger sensor s value exceeds the set value Service valve is closed Refrigerant is insufficient Refrigerant is overcharge Compressor lock Overload operation Compressor wiring is disconnected Power transistor is damaged Power source construction is defective Outdoor PCB is faulty C...

Page 52: ...N HEAT TIMER light 1 s digit Display pattern when in service mode Fan speed mode when there is an abnormal stop 2 time flash 3 time flash 4 time flash AUTO HI MED LO 5 time flash ULO 6 time flash 7 time flash operation mode and fan speed mode becomes as follows HI POWER ECONO Mode Operation mode Fan speed mode 0 5 sec 1 5 sec RUN light 10 s digit TIMER light 1 s digit 11 second interval 0 5 sec OF...

Page 53: ...84 94 55 45 35 25 15 5 5 15 25 35 45 55 65 75 85 95 56 46 36 26 16 6 6 16 26 36 46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 29 19 9 9 19 29 39 49 59 69 79 89 99 No does not sound Sensor name Room temperature sensor Indoor heat exchanger sensor Outdoor air temperature sensor Outdoor heat exchanger sensor 64ºC 64ºC 64ºC 64ºC ...

Page 54: ... 126 146 48 28 8 8 28 48 68 88 108 128 148 50 30 10 10 30 50 70 90 110 130 150 52 32 12 12 32 52 72 92 112 132 54 34 14 14 34 54 74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound Sensor value displayed when the error code is normal 64ºC 0 5 sec 0 1 sec 1 5 sec 11 second interval 0 5 sec OFF ON OFF ON OFF ON temperature information data Buzzer sound If ...

Page 55: ... 54 15 SR T 185 09 SRK DB 087D Service data record form 48 Operation mode Fan speed mode Wireless r Wireless r Wireless r Wireless r Wireless r wireless Wireless r ...

Page 56: ...70 0 10 Discharge pipe sensor temperature characteristics Indoor fan motor error Broken sensor wire connector poor connection 0 0 20 40 60 80 100 120 135 20 40 60 80 100 120 140 160 180 Temperature C Resistance k Defective fan motor connector poor connection defective indoor PCB 60 for the fan motor and indoor PCB check pro Power source reset Is it normalized Malfunction by temporary noise Replace...

Page 57: ...sor lock Compressor wiring short circuit Compressor output is open phase Outdoor PCB is faulty Service valve is closed EEV is faulty Compressor faulty Current safe stop Overload operation compressor lock overcharge 63 1 703Ω U V V W U W or more at 20ºC ...

Page 58: ... 57 15 SR T 185 09 SRK DB 087D Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 55 ...

Page 59: ...tive outdoor PCB Replace Defective outdoor PCB Replace NO YES Is the space for installation of indoor and or outdoor unit enough Is there any short circuit of air on indoor and or outdoor unit At heating does the indoor fan motor run Is the filter clogged Is there any liquid flooding Is there any anomalous sound on the compressor After resetting power for several times does it become normal Tempor...

Page 60: ...ipe sensor All modes Measuring point Resistance when normal Defrosting is performed for 10 minutes at approx 35 minutes Defrosting is performed for 10 minutes at approx 35 minutes Compressor stop The compressor cannot pick up its speed owing to the current safe so that the designed capacity is not achieved The compressor cannot pick up its speed owing to the heating overload protection so that the...

Page 61: ...d 20V Replace indoor PCB YES b Indoor unit fan motor check procedure 1 Indoor PCB output check 2 Fan motor resistance check FMI DC15V Indoor PCB DC 308 336V DC several V 4 6 V CNU GND Blue Yellow White Black Red Measuring point Resistance when normal Measuring point Voltage range when normal k M ...

Page 62: ...eration Faulty part other than fan motor YES Fan motor is faulty YES YES YES NO NO NO Replace the faulty part and the fuse Test run then the unit for checking Is there any damage on the internal circuit of fan motor Check the resistance value to judge See pages 60 to 63 Is the fuse blown on the indoor and outdoor PCB Is there any faulty part fan motor etc See pages 60 to 63 Replace the fuse on the...

Page 63: ... power transistor Remove the fasten terminal and test output voltage Inspection of outdoor fan motor See page 63 Check point of outdoor unit Color Color symbol OR Mark Brown BR Yellow Green Y G Black BK Blue BL White WH Red RD Orange Display Voltage range Voltage check in PCB The normal range is as follows DC280V DC230V DC310V DC220V DC218V DC222V DC213V DC212V DC214V DC215V DC214V DC216V DC225V D...

Page 64: ...on valve as a separate unit Measuring point Resistance when normal b Outdoor unit fan motor check procedure Measuring point Voltage range when normal DC15V DC several 4 7V Outdoor PCB GND DC308 336V CNFAN Red Black White Yellow Blae FM0 1 2 3 i ii iii DC iv i Fan motor resistance check Measuring point Resistance when normal k ii Black Black source ...

Page 65: ... thin part of remote control lower case with a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote control co terminal block Connect the terminal of remo with the terminal of indoor uni X and Y are no polarity Wiring route is as shown in th depending on the pulling out d The wiring inside the remote c The sheath...

Page 66: ...the terminal block Connect the terminal of remote control X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direction The wiring inside the remote control case should be within 0 3mm2 recommended to 0 5mm2 The sheath should be peeled off inside the remote control case The peeling off length of each wire is as...

Page 67: ...conds The indication changes to FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT by using button 5 Press SET button to fix 6 When UPPER LIMIT is selected valid during heating Press SET button to fix Indication example UPPER 26 C Displayed for two seconds After the fixed upper...

Page 68: ...n 04 accordingly You can select the louver stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the master remote control can be indicated Heating preparation indication should not be indicated Temperature indication is by degree C Temperature indication is by degree F ON OFF button finished Start St...

Page 69: ...5 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 5 C increase in return air temperature of indoor unit To be reset producing 2 0 C increase in return air temperature of indoor unit When heating thermostat is OFF fan...

Page 70: ...ON SET will be displayed Press SET button Selecct FUNCTION remote control function or I U FUNCTION indoor unit function Operation message Function description setting description Function No Fixing button Finishing button 7 2 1 Starting button Previous screen button Indoor unit selection button Press SET button 6 DATA LOADING Indication with blinking Display is changed to 01 7 DATA LOADING Blinkin...

Page 71: ... 70 15 SR T 185 eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL B PJZ012D077 b Model RC EX1A ...

Page 72: ... the Installation Manual should be given to a new owner WARNING Ask a professional contractor to carry out installation work according to the installation manual Improper installation work may result in electric shocks fire or break down Shut OFF the main power source before starting electrical work Otherwise it could result in electric shocks break down or malfunction Do not install the unit in a...

Page 73: ...ontrol to medical or communication equipment could disrupt medical activities video broadcasting or cause noise interference CAUTION Do not install the remote control at following places It could cause break down or deformation of remote control 1 Where it is exposed to direct sunlight 2 Near the equipment to generate heat 3 Where the surface is not flat Do not leave the remote control with its up...

Page 74: ... m 2 0 mm2 x 2 core 3 Remote control installation procedure Determine where to install the remote control Installation Using a switch box Installed directly on a wall Wiring direction Backward Upper center Upper left Cautions for selecting installation place 1 Installation surface must be flat and sufficiently strong R C case must not be deformed 2 Where the R C can detect room temperatures accura...

Page 75: ...n Installation procedure Dimensions Viewed from front Take care to protect the removed upper case from moisture or dust PCB side Viewed from rear To remove the upper case from the bottom cases of R C Insert the tip of flat head screwdriver or the like in the recess at the lower part of R C and twist it lightly to remove Connect wires from X and Y terminals of R C to X and Y terminals of indoor uni...

Page 76: ...om case In case of exposing wiring When the wiring is taken out from the upper center or upper left of R C Cut out the thin wall sections on the cases for the size of wire Upper center Upper left Upper case Bottom case When taking the wiring out from the upper center open a hole before separating the upper and bottom cases This will reduce risk of damaging the PCB and facilitate subsequent work Wh...

Page 77: ...r more R C Up to two units of R C can be used at the maximum for 1 indoor unit or 1 group One is main R C and the other is sub R C Operating range is different depending on the main or sub R C R C function Main Sub Run Stop setting temperature fan speed and flap direction operations High power and energy saving operations Energy saving setting R C sensor Test run menu operation Room temperature ra...

Page 78: ...e USB simultaneously with other USB devices It could cause malfunction or breakdown of R C or personal computer USB port Cover Note Initializing of password Administrator password for daily setting items and service password for installation test run and maintenance are used The administrator password at factory default is 0000 This setting can be changed Refer to User s Manual When the administra...

Page 79: ...ons Before use please read these Safety Precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken into consideration so be sure to observe them at all times Incorrect installation could lead to serious consequences such as death major injury or envirommental destruction Symbols used in these precautions After completed instal...

Page 80: ...unit approximately 1 8m Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the punch outs for the connection cables running into the casing with cutter Recess the electrical box procured locally and connection cables in the wall Mount the lower casing of the interface to the electrica...

Page 81: ... a external remote control unit procured locally to CNT terminal In case of the pulse input switch OFF the DIP switch SW2 1 on the interface PCB When setting operation permission prohibition mode switch OFF the DIP switch SW2 3 on the interface PCB Connection of Superlink E board Functions of CNT connector Switch ON the DIP switch SW2 2 Factory setting ON on the interface PCB Wiring connection bet...

Page 82: ...ll the wired remote control with reference to the attached instruction manual of wired remote control B 0 3mm2 x 2 core cable should be used for the wiring of wired remote control C Maximum length of wiring is 600m If the length of wiring exceeds 100m change the size of cable as mentioned below 100m 200m 0 5mm2 x 2 core 300m or less 0 75mm2 x 2 core 400m or less 1 25mm2 x 2 core 600m or less 2 0mm...

Page 83: ... 82 15 SR T 185 3 Superlink E board SC ADNA E WARING CAUTION 4 PJZ012D029CF ...

Page 84: ... 83 15 SR T 185 ...

Page 85: ...it 1 Place the unit as shown below 2 Remove the bottom plate and duct flange plate of rear from the unit Keep the removed tapping screws to reuse later The number of tapping screws to be removed BOTTOM TOP 3 Install rear panel by using removed tapping screws in process 2 Install fan guard by using tapping screws in parts set The number of tapping screws to be tightened BOTTOMAIR INLET KIT UT BAT1E...

Page 86: ...surface etc Run the sensor cable in a place where the power cable or electrical noise will not cause any abnormal operation 3 Installation procedure a Insert the tip of slotted screwdriver to the gap between the cover and base of the sensor box and twist it to disassemble b Fix the base to the wall with screws c Connect the cable to the terminal block in the base No polarity d Attach the cover to ...

Page 87: ...nnect the cable from remote sensor box and the cut wiring procedure 6 of CNG connector Non polarity Be sure to connect the wirings by solder separately Then wirings should prevent a short circuit separately by insulating tapes etc In case of faulty wiring connection it can cause electrical shock and fire j Put CNG connector back on the indoor unit PCB k Attach the control lid of the indoor unit 1 ...

Page 88: ...city for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heating Colder ...

Page 89: ...eclared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for hea...

Page 90: ...icy of continuous improvement we reserve the right to make changes in all specifications without notice C Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice C Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS LTD MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS LTD 16 5 Konan 2 chome Minato ku Tokyo 108 8215 Japan http www mhi m...

Reviews: