'20 • SR-SM-285
-
102
-
Error code
Remote control:
LED
Green
Red
Indoor
Content
E11
Address setting error of
indoor units
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Change of address setting
method
Set the address by DIP
switch SW2 on indoor unit
control PCB.
2. Error detection method
IU address has been set using
the “Master IU address set”
function of remote control.
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake of address setting
method
(
Address setting from remote
)
control can't be done.
Note:
Is “Master IU
address set” function of remote
control used?
E11 occurs
YES
IU
IU
IU
R/C
In case the wiring is below and “Mastar IU address
set” is used, E11 is appeared.