'20 • SR-SM-285
-
108
-
Error code
Remote control:
LED
Green
Red
Indoor
Content
E36
Discharge pipe
temperature error
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
* For the contents of control, refer to compressor overheat in the protective
control by controlling compressor rotation speed of microcomputer control
function for corresponding models.
Are the
characteristics of
discharge pipe temperature
sensor
normal?
Is the
discharge pipe temperature
control normal?
NO
YES
Is the
temperature (measured
actually) at detection of
error correct?
YES
YES
Is the
discharge pipe
temperature error persisted
during cooling / heating
operation?
NO
* For the characteristics of discharge
pipe temperature sensor, refer to E39.
YES
NO
NO
Replace discharge pipe
temperature sensor.
Insufficient refrigerant
amount : Recharge
refrigerant by weighing
proper amount on a scale.
Control operation check *
Defective outdoor unit
PCB
➞
Replace.
Check unit side:
• Isn’t filter clogged?
• Are indoor, outdoor
unit installation spaces
adequate?
• Isn’t there any short-
circuit of air?
• Isn’t there any fouling,
clogging on indoor heat
exchanger?
2. Error detection method
For the error detection method,
refer to compressor overheat
in the protective control by
controlling compressor rotation
speed of micro-computer control
function for corresponding
models.
3. Condition of error displayed
When discharge pipe
temperature anomaly is detected
2 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop.
4. Presumable cause
• Defective outdoor unit PCB
• Defective discharge pipe
temperature sensor
• Clogged filter
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
Note: