Error code
Remote control:
LED
Green
Red
Indoor
Content
E42
Current cut (1/2)
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
Power source
voltage OK?
YES
Are the
service valves
opened?
NO
YES
Is the
high pressure
during operation
OK?
YES
Is the
checked result of
insulation resistance and
resistance between terminals (1)
of compressor motor
OK?
YES
(1) 4.428Ω or more at 20°C
NO
NO
NO
To next page.
Check power source.
Open the valves.
Check refrigerant amount
and refrigerant circuit
* In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because liquid
refrigerant (migrated)
in the compressor is
discharged from the
compressor.
Replace compressor.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of error displayed
• If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
4. Presumable cause
• The valves closed
• Faulty power source
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module