'20 • SR-SM-285
-
118
-
Error code
Remote control:
LED
Green
Red
Content
Indoor
Stays OFF
Keeps flashing
E57
Insufficient refrigerant amount
or detection of service valve closure
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
NO
YES
Is the
service valve fully
opened?
Are the
connections of indoor
heat exchanger and/or return air
temperature sensor
connectors OK?
NO
YES
NO
YES
Are the
characteristics of indoor heat
exchanger and/or return air
temperature sensor
OK?
Is the low
pressure during operation
normal?
Indoor heat exchanger, return air temperature
sensor
Temperature-resistance characteristics
15
10
5
0
10
30
40
20
50
Temperature
sensor
resistance (k
Ω
)
Temperature (°C)
5k
Ω
at 25°C
(Broken wire)
(Short-circuit)
For the characteristics of indoor heat exchanger,
return air temperature sensor, see the following graph.
Open fully.
Correct indoor heat
exchanger, return air
temperature sensor
connector connections.
Defective indoor heat
exchanger, return air
temperature sensor
➞
Replace.
Charge refrigerant.
Defective indoor unit
control PCB
➞
Replace.
(Defective indoor heat
exchanger, return air
temperature sensor input
circuits)
2. Error detection method
• Judge insufficient refrigerant
amount by detecting the
temperature differnce between
indoor heat exchanger (Thi-R)
and indoor return air (Thi-A).
3. Condition of error displayed
When the insufficient refrigerant
amount is detected 3 times
within 60 minutes.
4. Presumable cause
• Defective indoor heat
exchanger temperature sensor
• Defective indoor return air
temperature sensor
• Defective indoor unit control
PCB
• Insufficient refrigerant amount
Note: When the compressor speed is 50 rps or under at 5 minutes after the start of compressor or the completion of defrost operation, the low refrigerant protection
control judges, by detecting the difference between the indoor heat exchanger temperature (Thi-R) and the indoor return air temperature (Thi-A), that it is in the
state of gas leakage, and stops the compressor.
Cooling: Indoor return air temperature (Thi-A) – Indoor heat exchanger temperature (Thi-R)
<
4 deg C
Heating: Indoor heat exchanger temperature (Thi-R) – Indoor return air temperature (Thi-A)
<
4 deg C