32
-
(i) In case of “Level input” setting (Factory default)
Input signal to CnT-6 or CnTA is OFF→ON …… unit ON
Input signal to CnT-6 or CnTA is ON→OFF …… unit OFF
Operation is not inverted.
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
Remote
control OFF
Remote
control ON
Remote
control OFF
Remote
control ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
CnT-6 or CnTA input
Unit A
Unit B
CnT-6 or CnTA input
Unit A
Unit B
Note (1) The latest operation has priority
It is available to operate/stop by remote control or central control.
(b) Input for external control
The external input for the indoor unit can be selected from the following input.
Input name
Content
1 Run/Stop
Refer to [(20) (c) Remote operation input]
2 Premission/Prohibition
Refer to [(21) Operation permission/prohibition]
3 Cooling/Heating
Refer to [(23) Selection of cooling/heating external input function]
4 Emergency stop
Indoor/outdoor units stop the operation, and [E63] is displayed.
5 Setting temperature shift
Set temperature is shifted by +2/-2°C in cooling/heating.
6 Forced thermo-OFF
Unit goes thermo off.
7 Temporary stop
Refer to [(22) Temporary stop input]
8 Silent mode
Outdoor unit silent mode is activated.
(ii) In case of “Pulse input” setting (Local setting)
It is effective only when the input signal to CnT-6 or CnTA is changed OFF→ON, and at that time unit operation [ON/OFF]
is inverted.
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
Remote
control OFF
Remote
control ON
Remote
control OFF
Remote
control ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
CnT-6 or CnTA input
Unit A
Unit B
CnT-6 or CnTA input
Unit A
Unit B
(c) Remote operation
(i) In case of multiple units (Max. 16 indoor units group) are connected to one wired remote control
When the R/C function setting of wired remote control for “External control set” is changed from “Individual (Factory
default)” to “ For all units”, all units connected in one wired remote control system can be controlled by external
operation input.
XY
Wired remote control
Indoor unit
Signal &
Power
XY
123
123
XY
123
123
XY
123
123
XY
123
123
XY
123
123
Indoor unit
①
Outdoor unit Outdoor unit Outdoor unit Outdoor unit
Outdoor unit
Indoor unit
②
Indoor unit
③
Indoor unit
Ⓕ
Ex. Indoor units =
+①+②+③+……Ⓕ ≦16 units
0
Cn
External
input
0
Refrigerant
piping