2.2.2 Troubleshooting flow
(1) List of troubles
Remote control display
Description of trouble
Reference page
None
Operates but does not cool.
80
None
Operates but does not heat.
81
None
Earth leakage breaker activated
82
None
Excessive noise/vibration (1/3)
83
None
Excessive noise/vibration (2/3)
84
None
Excessive noise/vibration (3/3)
85
None
Louver motor failure
86
None
Power source system error (Power source to indoor unit control PCB)
87
None
Power source system error (Power source to remote control)
88
INSPECT I/U
INSPECT I/U (When 1 or 2 remote controls are connected)
89
INSPECT I/U
INSPECT I/U (Connection of 3 units or more remote controls)
90
WAIT
Communication error at initial operation
91
-
93
None
No display
94
E1
Remote control communication circuit error
95
E5
Communication error during operation
96
E6
Indoor heat exchanger temperature sensor anomaly
97
E7
Return air temperature sensor anomaly
98
E8
Heating overload operation
99
E9
Drain trouble
100
E10
Excessive number of connected indoor units (more than 17 units) by controlling with one remote control
101
E11
Address setting error of indoor units
102
E16
Indoor fan motor anomaly
103
E19
Indoor unit operation check, drain pump motor check setting error
104
E20
Indoor fan motor rotation speed anomaly
105
E28
Remote control temperature sensor anomaly
106
E35
Cooling overload operation
107
E36
Discharge pipe temperature error
108
E37
Outdoor heat exchanger temperature sensor anomaly
109
E38
Outdoor air temperature sensor anomaly
110
E39
Discharge pipe temperature sensor anomaly
111
E40
Service valve (gas side) closing operation
112
E42
Current cut
113
・
114
E47
Active filter voltage error
115
E48
Outdoor fan motor anomaly
116
E51
Power transistor anomaly
117
E57
Insufficient refrigerant amount or detection of service valve closure
118
E58
Current safe stop
119
E59
Compressor startup failure
120
E60
Compressor rotor lock error
121