'20 • SR-SM-285
-
92
-
Error code
Remote control:
LED
Green
Red
Indoor
Stays OFF
Keeps flashing
Content
WAIT
Communication error at
initial operation (2/3)
1. Applicable model
5. Troubleshooting
All Models
When the fuse is blown, the
method to inspect inverter
before replacing the power
source fuse
Diagnosis
Countermeasure
Replace the outdoor
unit PCB
NO
YES
NO
Replace the outdoor
unit PCB
YES
Replace the
reactor.
Is there
a short-circuit between phases of
outdoor unit PCB?
Are there
cracks or burning on the power
transistor module or diode
stack?
Is reactor the anomalous?
NO
YES
Replace fuse.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Blown fuse
• Faulty outdoor unit PCB
• Faulty reactor
Note:
Summary of Contents for SRR25ZS-W
Page 79: ... 20 SR SM 285 78 ...