'20 • SR-SM-285
-
9
-
(b) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the previous
operation mode, changes the operation mode.
(c) When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is se-
lected during heating, cooling or dehumidifying operation, the unit is operated in the previous operation mode.
(d) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the sig-
nals of the wireless remote control and the setting temperature.
(e) When the unit is operated automatically with the wired remote control connected, the cooling operation is controlled ac-
cording to the display temperatures while the setting temperature is compensated by +1°C during dehumidifying or by +2°C
during heating.
(14) Outline of automatic operation
(a) Determination of operation mode
The unit checks the indoor air temperature and the outdoor air temperature, determines the operation mode, and then be-
gins in the automatic operation.
27.5
25.5
19.5
18
A
30
Heating
Dehumidifying
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
(i)
(ii)
(iii)
When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
When the operation mode has been judged following the change of setting temperature with the remote control, the hourly
judgment of operation mode is cancelled.
If the setting temperature is changed with the wireless remote control, the operation mode is judged immediately.
Signals of wireless remote control (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
temperature
Cooling
18
19
20
21
22
23
24
25
26
27
28
29
30
Dehumidifying
19
20
21
22
23
24
25
26
27
28
29
30
31
Heating
20
21
22
23
24
25
26
27
28
29
30
31
32
Unit : ºC
(a) Frost prevention control
(During cooling or dehumidifying)
(15) Protective control function
(17) Frost prevention control
( i ) Operating conditions
( ii ) Detail of anti-frost operation
(iii) Reset condition
Indoor heat exchanger
temperature (ºC)
2.5
8
Operation mode
Item
Protective control
Reset
Compressor operation
Indoor fan
Forced outage
Operation instruction
Depends on operation mode
8
2.5
1)
2)
Reset
Protective
control