'13 • PAC-T-197
Preset point of the protective devices
Parts name
Mark
Equipped
unit
40, 50, 60 model
71, 100, 125, 140 model
Thermistor
(for protection
overloading in heating)
ThI-R
〔
TH1
〕
ThI-R
〔
TH2
1
〕
Indoor unit
Thermistor
(for frost prevention)
Thermistor
(for protection high
pressure in cooling.)
Tho-R
(TH1)
Outdoor unit
ON 65
℃
OFF 51
℃
ON 63
℃
OFF 53
℃
Thermistor
(for detecting discharge
pipe temp.)
Tho-D
(TH3)
Outdoor unit
ON 115
℃
OFF 85
℃
ON 115
℃
OFF 95
℃
―
―
High pressure switch
(for protection)
63H1
Outdoor unit
ON 4.15MPa
OFF 3.15MPa
Low pressure sensor
(for protection)
LPT
Outdoor unit
ON 0.079MPa
OFF 0.227MPa
Notes(1) Values in ( ) shown in the case of 40, 50, 60 models.
(2) Values in
〔 〕
shown in the case of SRK.
ON 63
℃
OFF 56
℃
ON 17
℃
OFF 16
℃
ON 1.0
℃
OFF 10
℃
ON 2.5
℃
OFF 8
℃