210
-
'13 • PAC-T-197
'10 • PAC-DB-136
1.9.2 Correction of cooling and heating capacity in relation to air flow rate control
(fan speed)
1.9.3 Correction of cooling and heating capacity in relation to one way length of
refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Note (1) Calculate the equivalent length using the following formula.
However, install the piping so that the piping length is 5 m of the limit length (actual length) for the respective types.
• Equivalent length =Actual (Equivalent bend length x number of bends in the piping.)
Equivalent length per bend. (Model 71-140 only)
(1) Models 40-60
(2) Models 71-140
0.20
0.25
0.30
Gas pipe diameter (mm)
Equivalent bend length
φ
19.05
φ
15.88
φ
12.7
1.00
0.97
0.95
Fan speed
Coefficient
Lo
Me
P-Hi or Hi
(
1
)
55
0.988
0.933
0.870
0.824
0.810
0.979
0.963
0.941
0.935
40
45
50
0.993
0.954
0.910
0.878
0.868
0.988
0.980
0.967
0.964
0.993
0.947
0.897
0.860
0.849
0.985
0.974
0.958
0.954
0.988
0.940
0.883
0.842
0.829
0.982
0.969
0.950
0.945
30
35
0.998
0.968
0.937
0.914
0.907
0.994
0.991
0.984
0.983
0.998
0.961
0.924
0.896
0.888
0.991
0.985
0.975
0.973
15
20
25
1
0.989
0.978
0.968
0.966
1.003
1.007
1.009
1.011
1
0.982
0.964
0.950
0.946
1
1.002
1.001
1.002
1
0.975
0.951
0.932
0.927
0.997
0.996
0.992
0.992
7.5
10
1
1
1
1
1
1.008
1.016
1.022
1.026
1
0.996
0.991
0.986
0.985
0.680
0.654
0.662
0.634
0.644
0.615
0.716
0.693
0.698
0.673
0.770
0.751
0.752
0.732
0.734
0.712
0.788
0.771
0.806
0.968 0.963 0.963
0.973 0.968
0.978 0.978 0.973
0.983
0.983
0.762 0.749 0.736
0.789 0.776
0.829 0.816 0.803
0.843
0.856
0.932 0.929 0.926
0.940 0.936
0.951 0.948 0.944
0.955
0.959
0.897 0.892 0.887
0.908 0.902
0.924 0.919 0.912
0.929
0.935
0.882 0.876 0.870
0.894 0.888
0.913 0.907 0.900
0.920
0.928
0.790
1.006
1.013
1.018
1.021
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
105
ー
ー
90
95
100
ー
ー
ー
ー
ー
ー
80
85
ー
ー
ー
ー
65
70
75
ー
ー
ー
ー
ー
ー
60
ー
ー
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
Note (1) SRK series only.
5m
10m
15m
20m
25m
30m
0.99
0.98
0.97
0.96
0.95
0.94
When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in
heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
1.9.4 Height difference between the indoor unit and outdoor unit
Adjustment coefficient
7
10
15
20
25
30
1
1
1
1
1
1
1
0.99 0.975 0.965 0.95 0.935
Piping length (m)
Heating
Cooling
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...