23
-
'13 • PAC-T-197
Model
Item
FDT140VSXPVF1
Indoor unit
FDT71VF1 (2 units)
Outdoor unit
FDC140VSX
Power source
3 Phase 380-415V 50Hz / 380V 60Hz
Operation
data
Nominal cooling capacity (range)
kW
14.0 [ 5.0(Min.)~ 16.0(Max.)]
Nominal heating capacity (range)
kW
16.0 [ 4.0(Min.)~ 20.0(Max.)]
Power
consumption
Cooling
kW
3.88
Heating
3.70
Max power consumption
6.79
Running
current
Cooling
A
5.7 / 6.0
Heating
5.4 / 5.7
Inrush current, max current
5 , 15
Power factor
Cooling
%
98
Heating
99
EER
Cooling
3.61
COP
Heating
4.32
Sound power level
Cooling
dB(A)
64
72
Heating
Sound pressure level
Cooling
P-Hi : 46 Hi : 35 Me : 33 Lo : 31
49
Heating
52
Silent mode sound pressure level
—
—
Exterior dimensions (Height x Width x Depth)
mm
Unit 246 × 840 × 840
Panel 35 × 950 × 950
1300×970×370
Exterior appearance
( Munsell color )
Plaster White
( 6.8Y8.9/0.2 ) near equivalent
Stucco White
( 4.2Y7.5/1.1 ) near equivalent
Net weight
kg
UNIT 24 PANEL 5.5
105
Compressor type & Q'ty
—
RMT5134MDE3×1
Compressor motor (Starting method)
kW
—
Direct line start
Refrigerant oil (Amount, type)
—
0.9 M-MA68
Refrigerant (Type, amount, pre-charge length)
kg
R410A 4.5kg(Pre-charged up to the piping length of 30m)Outdoor unit
Heat exchanger
Louver fin & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
Electronic expansion valve
Fan type & Q'ty
Turbo fan ×1
Propeller fan ×2
Fan motor (Starting method)
W
50 < Direct line start >
86 × 2 < Direct line start >
Air flow
Cooling
m
3
/min
P-Hi : 28 Hi : 21 Me : 19 Lo : 17
100
Heating
Available external static pressure
Pa
0
—
Outside air intake
Possible
—
Air filter, Quality / Quantity
Pocket plastic net ×1(Washable)
—
Shock & vibration absorber
Rubber sleeve(for fan motor)
Rubber sleeve(for compressor )
Electric heater
W
—
20(Crank case heater)
Operation
control
Remote control
(option) wired : RC-EX1A , RC-E5 , RCH-E3 wireless : RCN-T-36W-E
Room temperature control
Thermostat by electronics
Operation display
—
Safety equipments
Overload protection for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Abnormal discharge temperature protection.
Installation
data
Refrigerant piping size ( O.D. )
mm
Liquid line: I.U.
φ
9.52 (3/8")
②φ
9.52(3/8") × 0.8
①φ
9.52(3/8") × 0.8 O.U.
φ
9.52 (3/8")
Gas line: I/U
φ
15.88 (5/8")
②φ
15.88(5/8") × 1.0
①φ
15.88(5/8") × 1.0 O/U
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Attached length of piping
m
—
—
Insulation for piping
Necessary (both Liquid & Gas lines)
Refrigerant line (one way) length
m
Max.100m
Vertical height diff. between O.U. and I.U.
m
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
Drain hose
Hose connectable VP25(O.D.32)
Holes size
φ
20 × 3pcs
Drain pump, max lift height
mm
Built-in Drain pump , 700
—
Recommended breaker size
A
—
L.R.A. (Locked rotor ampere)
A
5.0
Interconnecting wires
Size x Core number
φ
1.6mm × 3 cores (Including earth cable) / Termainal block (Screw fixing type)
IP number
IPX0
IP24
Standard accessories
Mounting kit, Drain hose
Edging
Option parts
—
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.
(6) The operation data indicate when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(7) Indoor unit specifications for one unit. Capacity and operation data are two indoor units are combined and run together.
(8) Branching pipe set "DIS-WA1"×1(option).
①
: Pipe of O.U.~Branch,
②
: Pipe of Branch~I.U.
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO5151-T1
Heating
20˚C
—
7˚C
6˚C
The pipe length is 7.5m.
D
PJF000Z315
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...