309
-
'13 • PAC-T-197
(1) Auto operation
(a)
If “Auto” mode is selected by the remote control, the heating and the cooling are automatically switched according to the
difference between outdoor air temperature and setting temperature and the difference between setting temperature and return
air temperature. (When the switching of cooling mode
↔
heating mode takes place within 3 minutes, the compressor does
not operate for 3 minutes by the control of 3-minute timer.) This will facilitate the cooling/heating switching operation in
intermediate seasons and the adaptation to unmanned operation at stores, etc (ATM corner of bank).
Notes (1) Temperature range of switching cooling/heating mode can be changed by RC-EX1A from ±1.0
~
±4.0.
(2) Room temperature control during auto cooling/auto heating is performed
according to the room temperature setting temperature. (DIFF: ±1 deg)
(3) If the indoor heat exchanger temperature rises to 59°C or higher during
heating operation, it is switched automatically to cooling operation. In
addition, for 1 hour after this switching, the heating operation is not
performed, regardless of the temperature shown at right.
Room temperature setting temperature
+3
-3
Cooling operation
Heating operation
Room temperature (detected with Th
I
-A) [deg]
59
56
Heating operation stopped (cooling)
Heating OK
Indoor heat exchanger temperature (°C)
(b) The following automatic controls are performed other than (a) above.
(i) Cooling or heating operation mode is judged according to the conditions of the "Judgment based on Setting tempe
Cooling select temperature and Indoor return air temperature" and the "Judgment based on Outdoor temperature".
1)
In "Setting temperature - Cooling select temperature < Indoor return air temperature" and "Outdoor temperature/Cooling < Outdoor
return air temperature"
⇒
Operation mode: Cooling
2)
"Setting tempe Heating select temperature > Indoor return air temperature" and "Outdoor temperature/Heating >
Outdoor air temperature"
⇒
Operation mode: Heating
3) The outdoor air temperature of the above judgment conditions is sampled at every 10 minutes.
4) In the range where the above cooling and heating zones are overlapped
⇒
Forced thermostat OFF
Indoor return air temperature (
℃
)
O
ut
do
or
ai
r
te
m
pe
ra
tu
re
(
℃
)
24
26
12
14
16
18
28
30
20
22
12
26
24
22
20
18
16
14
30
28
Heating
Cooling
Forced thermostat OFF
Forced thermostat
OFF
Forced
thermostat OFF
Outdoor temperature/Heating
Outdoor temperature/Cooling
Cooling select temperature
Heating select temperature
Setting temperature
1.11.3 Operation control function by the indoor control
(
Ⅰ
) FDT, FDTC, FDEN, FDU, FDUM, FDF series
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...