'13 • PAC-T-197
(i) In case of “Level input” setting (Factory default)
Input signal to CnT-6 or CnTA is OFF→ON …… unit ON
Input signal to CnT-6 or CnTA is ON→OFF …… unit OFF
Operation is not inverted.
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
Remote
control OFF
Remote
control ON
Remote
control OFF
Remote
control ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
CnT-6 or CnTA input
Unit A
Unit B
CnT-6 or CnTA input
Unit A
Unit B
Note: The latest operation has priority
It is available to operate/stop by remote control or center control
(ii) In case of “Pulse input” setting (Local setting)
It is effective only when the input signal to CnT-6 or CnTA is changed OFF→ON, and at that time unit operation [ON/
OFF] is inverted.
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
Remote
control OFF
Remote
control ON
Remote
control OFF
Remote
control ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
CnT-6 or CnTA input
Unit A
Unit B
CnT-6 or CnTA input
Unit A
Unit B
(c) Remote operation
(i) In case of multiple units (Max. 16 indoor units group) are connected to one wired remote control
When the indoor function setting of wired remote control for “External control set” is changed from “Individual
(Factory default)” to “ For all units”, all units connected in one wired remote control system can be controlled by
external operation input.
Individual operation (Factory default)
All units operation (Local setting)
CnT-6 or
CnTA
ON
OFF
ON
OFF
Only the unit
directly connected
to the remote control
can be operated.
Only the unit
directly connected
to the remote
control can be
stopped opeartion.
All units in one
remote control
system can be
operated.
All units in one
remote control
system can be
stopped operation.
Unit
①
only
Unit
①
only
Units
①-Ⓕ
Units
①-Ⓕ
When more than one indoor unit (Max. 16 indoor units) are connected in one wired remote control system:
(1) With the factory default, external input to CnT-6 or CnTA is effective for only the unit
①
.
(2) When setting “For all unit” (Local setting), all units in one remote control system can be controlled by external
input to CnT-6 or CnTA on the indoor unit
①
.
(3) External input to CnT-6 or CnTA on the other indoor unit than the unit
①
is not effective.
Ex. Indoor units =
⓪+①+②+③x3+……Ⓕ ≦16 units
XY
Wired remote controller
Refrigerant piping
Indoor unit
⓪
Signal &
Power
XY
123
123
XY
123
123
XY
123
123
XY
123
123
XY
123
123
XY
123
XY
123
Indoor unit
①
Outdoor unit
⓪
Outdoor unit
①
Outdoor unit
②
Outdoor unit
③
Outdoor unit
Indoor unit
②
Indoor unit
③
䇭
(master)
Indoor unit
Ⓕ
Indoor unit
③
䇭
(slave)
Indoor unit
③
䇭
(slave)
C
n
External
input
Ⓕ
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...