'13 • PAC-T-197
(7) Indoor fan motor protection
When the air conditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300 min
-1
or
under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
(8) Serial signal transmission error protection
(a)
Purpose:
Prevents malfunction resulting from error on the indoor
↔
outdoor signals.
(b)
Detail of operation:
If the compressor is operating and a serial signal cannot be received from the indoor control with outdoor
control having serial signals continues for 7 minute and 35 seconds, the compressor is stopped. After the
compressor has been stopped, it will be restarted after the compressor start delay if a serial signal can
be received again from the indoor control.
(9) Plural unit control – Control of 16 units group by one remote control
(a) Function
One remote control switch can control a group of multiple number of unit (Max. 16 indoor units). “Operation mode”
which is set by the remote control switch can operate or stop all units in the group one after another in the order of unit
No.
(1)
. Thermostat and protective function of each unit function independently.
Note (1) Unit No. is set by SW1 on the interface PCB. Unit No. setting by SW1 is necessary for the interface only. In cases of the twin and triple
specification, it is necessary set for the master and the slave units. This can be selected by SW3. (All are set for the master unit at the shipping
from factory.)
SW1: For setting of 0 – 9, A – F
SW3: For setting of master and slave units
(See table shown at right.)
(2) Unit No. may be set at random unless duplicated, it should be better to set orderly like 0, 1, 2…, F to avoid mistake.
(b) Display to the remote control
(i) Center or each remote control basis, heating preparation: the youngest unit No. among the operating units in the
remote mode (or the center mode unless the remote mode is available) is displayed.
(ii) Inspection display, filter sign: Any of unit that starts initially is displayed.
(iii) Confirmation of connected units
1)
In case of RC-EX1A remote control
If you touch the buttons in the order of “Menu”
→
“Next”
→
“Service & Maintenance”
→
“IU address” on the
TOP screen of remote control, the indoor units which are connected are displayed.
2)
In case of RC-E5 remote control
Pressing “AIR CON No.” button on the remote control displays the indoor unit address. If “
▲
” “
▼
” button is
pressed at the next, it is displayed orderly starting from the unit of youngest No.
Indoor unit
Outdoor unit
Signal wiring
between outdoor unit
and indoor units
Connection cable
(Master unit)
(Slave unit 1)
(Slave unit 2)
Refrigerant piping
Remote control
Remote control wiring
R
Interfase kit
(Master)
(Slave 1)
(Slave 2)
0
1
2
3
F
4
4
4
*1
*1
*1
*1
*1
*2
*2
*2
*1:In case of SRK, SRF single use.
*2:In case of SRK triple use.
SW3 setting (For interface PCB)
SW3-1
SW3-2
Master
OFF
OFF
Stave1
OFF
ON
Stave2
ON
OFF
Switch
Unit
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...