330
-
'13 • PAC-T-197
(13) Dew prevention control
Ⅱ
[Cooling]:Prevents dewing on the indoor unit.
(a) Operating conditions:
When the following conditions have been met for more than 30 minutes after starting operation
(i) Compressor's command speed is 28 rps or higher.
(ii) Detected value of humidity is 68% or higher.
(b) Contents of operation
(i) Air capacity control
Note (1) Ranges A and B are as shown below.
Humidity(%)
68
73
Range A
Range B
Model
Item
SRK50, 60
LO
Upper limit of compressor's command speed
RangeA: 50rps, RangeB: 30rps
Indoor fan
5th speed
AUTO,HI,MED
Upper limit of compressor's command speed
RangeA: 50rps, RangeB: 30rps
Indoor fan
Adaptable to compressor's command
speed (5th to 9th speed)
(ii) When this control has continued for more than 30 minutes continuously,the following wind direction control is per-
formed.
1) When the vertical wind direction is set at other than the vertical swing,the flaps change to the horizontal position.
(c) Resetting condition:
When any of followings is metdirec
(i) Compressor's command speed is less than 28 rps.
(ii) Detected value of humidity is less than 63%.
(a) Purpose of DRY mode
(b) Outline of control
The purpose is "Dehumidification", and not to control the humidity to the target condition.
Indoor/outdoor unit control the operation condition to reduce the humidity, and also prevent over cooling.
(i) Indoor unit fan speed and compressor are controlled by the area which is selected by the temp. difference.
Indoor unit fan speed
D
A
Me speed
Indoor unit
fan speed
STOP
Compressor
speed
STOP
Difference between set temp. and return temp.
(ii) The indoor unit check the current area by every 5 minutes, and operate by the next checking.
(14) Outline of dry(dehumidifying) operation
Limited (Lower than
normal cooling operation)
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...