(16) Refrigeration cycle system protection
(a) Starting conditions
1) When 5 minutes (Heating : 9 minutes) have elapsed after the compressor ON or the completion of the defrost control
2) Other than the defrost control
3) When, after meeting the conditions of 1) and 2) above, the compressor speed, indoor air temperature (ThI-A) and
indoor heat exchanger temperature (ThI-R) have met the conditions in the following table for 5 minutes:
Notes (1) Except that the fan speed is HI in heating operation and silent mode control.
(b) Contents of control
1) When the conditions of 1) above are met, the compressor stops.
2) Error stop occurs when the compressor has stopped 3 times within 60 minutes.
(c) Resetting condition
When the compressor has been turned OFF
Compressor speed (N)
Operation mode
Cooling
Heating(1)
Indoor air temperature (ThI-A)
ThI-A−4<ThI-R
Indoor air temperature (ThI-A)/
Indoor heat exchanger temperature (Th
I-R
)
ThI-R<ThI-A+4
<
=
10
ThI-A 40
<
=
<
=
0
ThI-A 40
<
=
40
N
<
=
40
N
<
=