349
-
'13 • PAC-T-197
Remote control
Indoor control PCB
Outdoor control PCB
Location of
trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED (1)
Red LED
Green
LED (1)
Keeps
flashing
1(2)-time
flash
Keeps
flashing Stays OFF
Keeps
flashing
Fan motor
• Indoor fan motor rotation speed anomaly
Replacement, repair
417
Indoor power PCB • Defective indoor power PCB
Replacement
1-time
flash
Keeps
flashing Stays OFF
Keeps
flashing
Panel switch
detection
• Defective panel switch operation (FDT only)
Repair
418
Stays OFF
Keeps
flashing Stays OFF
Keeps
flashing
Remote control tem-
perature thermistor • Broken wire of remote control temperature thermistor
Repair
419
Note (1)
Normal indicator lamp (Indoor, outdoor units: Green) extinguishes (or lights continuously) only when CPU is anomalous. It keeps
flashing in any trouble other than anomalous CPU.
(2) * mark in the Description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing
the part, it is judged consequently that the replaced part was defective.
Remote control
Indoor unit display
Outdoor control PCB
Location of
trouble
Description of trouble
Repair method
Reference
page
Error code Red LED RUN light TIMER light Red LED Green LED
No-indication Stays OFF
Stays OFF
Stays OFF
Keeps
flashing
—
ON
—
—
—
—
—
—
—
—
—
—
—
—
•Normal operation
—
—
456
457
458
465
466
467
469
470
471
472
459
−
463
2-time
flash
Stays OFF Indoor unit power
supply
•Power OFF, broken wire/blown fuse, broken transformer wire
Repair
Keeps
flashing
Remote control
wires
•Poor connection, breakage of remote control wire * For wire breaking at power ON, the
LED is OFF.
Repair
Remote control
• Defective remote control PCB
Replacement of
remote control
WAIT
or
INSPECT I/U
2-time
flash
Keeps
flashing
Indoor-outdoor
units connection
wire
• Poor connection, breakage of indoor-outdoor units connection wire
Repair
Remote control • Improper setting of master and slave by remote control
Keeps
flashing
Stays OFF
Keeps
flashing
Remote control
wires (Noise)
•Poor connection of remote control signal wire (White)
•Intrusion of noise in remote control wire
* For wire breaking at power ON, the LED is OFF
Repair
Remote control
indoor control PCB
*
• Defective remote control or indoor control PCB (defective communication circ uit)?
Replacement of
remote control or
PCB
2 -time
flash
Keeps
flashing
Indoor-outdoor
units connection
wire
•Poor connection of wire between indoor-outdoor units during operation
(disconnection, loose connection)
•Anomalous communication between indoor-outdoor units by noise, etc.
Repair
Stays OFF
Keeps
flashing
(Noise)
•CPU-runaway on outdoor control PCB
Power reset or
Repair
Outdoor control
PCB
*
•Occurrence of defective outdoor control PCB on the way of power supply (defective com-
munication circuit)?
Replacement of
PCB
6-time
flash
6
flash
6
flash
ON
ON
ON
Stays OFF Stays OFF
Outdoor control
PCB
•Defective outdoor control PCB on the way of power supply
Replacement
Fuse
•Blown fuse
Stays OFF
Keeps
flashing
Number of con-
nected indoor units
•When multi-unit control by remote control is performed, the number of
units is over
Repair
468
6-time
flash
ON
Stays OFF
Keeps
flashing
Fan motor
•Defective fan motor
Replacement, repair
Replacement, repair
Indoor control PCB
•Defective indoor control PCB
Replacement
Stays OFF
Keeps
flashing
Remote control
temperature therm-
istor
• Broken wire of remote control temperature thermistor
Repair
Note (1) *mark in the Description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing
the part, it is judged consequently that the replaced part was defective.
1-time flash
Stays OFF
Keeps
flashing
Indoor heat
exchanger tempera
ture sensor 1
Indoor room
temperature sensor
•Defective indoor heat exchanger temperature sensor 1
(defective element, broken
wire, short-circuit)
• Poor contact of temperature sensor 1 connector
Replacement, repair
of temperature
sensor 1
Indoor control PCB
•Defective indoor control PCB (Defective temperature sensor 1 input
circuit)?
Replacement of
PCB
ON
Stays OFF
Keeps
flashing
Stays OFF
Keeps
flashing
Limit switch,
air inlet panel
•Limit switch operate
•Defective limit switch
(Poor contact of limit switch connector)
•Set is defective air inlet panel
Indoor control PCB
•Defective indoor control PCB (Defective limit switch input circuit)?
Replacement of
PCB
3-time
flash
2-time
flash
Stays OFF
ON
ON
Keeps
flashing
Stays OFF
Keeps
flashing
Indoor heat
exchanger tempera
ture sensor 2
•
(defective element, broken
•
Replacement, repair
of temperature
sensor 2
Indoor control PCB
Indoor control PCB
•
Replacement of
PCB
Replacement, repair
of temperature
sensor
Replacement of
PCB
Stays OFF
Keeps
flashing
Indoor unit No. set-
ting
•No master is assigned to slaves.
Repair
Rcmote control wires •Anomalous remote control wire connection, broken wire between master and slav e units
-time
-time
—
—
Defective indoor heat exchanger temperature sensor 2
wire, short-circuit)
Poor contact of temperature sensor 2 connector
Defective indoor control PCB (Defective temperature sensor 2 input
circuit)?
•
•
※
•
Defective indoor room temperature sensor
(defective element, broken wire,
short-circuit)
Poor contact of temperature sensor connector
Defective indoor control PCB (Defective temperatuer sensor input circuit)?
Stays OFF
No-indication
2) SRK series
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...