(iv) Inspection procedures corresponding to detail of trouble
Sensor error
Indoor fan motor error
Broken sensor wire,
connector poor connection
Defective fan motor, connector poor
connection, defective indoor PCB
368 for the fan motor and indoor PCB check
Power supply reset
Is it normalized?
Malfunction by temporary noise
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor PCB.)
procedure.
Sensor temperature characteristics (Room
temp., indoor heat exchanger temp.)
Temperature (˚C)
Resistance (k
)
30
25
20
15
10
5
30
20
10
40
50
60
70
0
-10