'13 • PAC-T-197
1.12.2 Troubleshooting flow
(1) List of troubles
a) FDT, FDTC, FDEN, FDU, FDUM, FDF series
Remote controller display
Description of trouble
Reference page
None
Operates but does not cool.
387
None
Operates but does not heat.
388
None
Earth leakage breaker activated
389
None
Excessive noise/vibration (1/3)
390
None
Excessive noise/vibration (2/3)
391
None
Excessive noise/vibration (3/3)
392
None
Louver motor failure (FDT, FDTC, FDEN, FDF series)
393
None
Power supply system error (Power supply to indoor control PCB)
394
None
Power supply system error (Power supply to remote control)
395
INSPECT I/U
INSPECT I/U (When 1 or 2 remote controls are connected)
396
INSPECT I/U
INSPECT I/U (Connection of 3 units or more remote controls)
397
WAIT
Communication error at initial operation (Models SRC40-60 only)
398
‐
400
WAIT
Communication error at initial operation (Models FDC71-140 only)
401
‐
403
None
No display
404
E1
Remote controller communication circuit error
405
E5
Communication error during operation
406
E6
Indoor heat exchanger temperature thermistor anomaly
407
E7
Return air temperature thermistor anomaly
408
E8
Heating overload operation
409
E9
Drain trouble
410
E10
Excessive number of connected indoor units (more than 17 units) by controlling with one remote control
411
E11
Address setting error of indoor units
412
E14
Communication error between master and slave indoor units
413
E16
Indoor fan motor anomaly
414
E18
Address setting error of moster and slave indoor unit
415
E19
Indoor unit operation check, drain motor check setting error
416
E20
Indoor fan motor rotation speed anomaly
417
E21
Defective panel switch operation (FDT only)
418
E28
Remote control temperature thermistor anomaly
419
E35
Cooling overload operation (Models SRC40-60 only)
420
E35
Cooling overload operation (Models FDC71-140 only)
421
E36
Discharge pipe temperature error
422
E37
Outdoor heat exchanger temperature thermistor anomaly
423
E38
Outdoor air temperature thermistor anomaly
424
E39
Discharge pipe temperature thermistor anomaly
425
E40
Service valve (gas side) closing operation (Models SRC40-60 only)
426
E40
High pressure error (63H1 activated) (Models FDC71-140 only)
427
E41
Power transistor overheat (Models FDC71-140 only)
428
E42
Current cut
429
・
430
E45
Communication error between inverter PCB and outdoor control PCB (Models FDC71-140 only)
431
E47
Inverter over-current error (Models SRC40-60 only)
432
E47
Inverter PCB A/F module anomaly (Model FDC71 only)
433
E48
Outdoor fan motor anomaly (Models SRC40-60 only)
434
E48
Outdoor fan motor anomaly (Models FDC71-140 only)
435
E49
Low pressure error or low pressure sensor anomaly (Models FDC71-140 only)
436
・
437
E51
Power transistor anomaly (Models SRC40-60 only)
438
E51
Inverter and fan motor anomaly (Models FDC71-140 only)
439
E53
Suction pipe temperature thermistor anomaly (Models FDC71-140 only)
440
E54
Low pressure sensor anomaly (Models FDC71-140 only)
441
E57
Insufficient refrigerant amount or detection of service valve closure (Models SRC40-60 only)
442
E57
Insufficient refrigerant amount or detection of service valve closure (Models FDC71-140 only)
443
E58
Current safe stop (Models SRC40-60 only)
444
E59
Compressor startup failure (Models SRC40-60 only)
445
E59
Compressor startup failure (Models FDC71-140 only)
446
・
447
E60
Anomalous compressor rotor lock (Models SRC40-60 only)
448
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...