398
-
'13 • PAC-T-197
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
–
2-time flash
Stays OFF
Keeps flashing
Content
WAIT
Communication error at
initial operation (1/3)
(Models SRC40-60)
1. Applicable model
5. Troubleshooting
Models SRC40-60
When the remote control LCD
displays “
WAIT
” 2
minutes after the power on.
Diagnosis
Countermeasure
Replace the
power supply fuse.
NO
YES
YES
NO
YES
YES
The remote controller LCD
displays “ ”
2 minutes after the power on.
Turn the breaker off once and then
back on again 3 minutes later.
Is normal condition restored?
YES
YES
NO
NO
NO
NO
YES
NO
Isn’t blown
the power supply fuse (20A) on the outdoor
unit controller?
Is AC220/240V
detected at the secondary side of
outdoor sub PCB?
Are OK the
connection wires between the
outdoor sub and the main
PCB’S?
NO
Isn’t F10 fuse (250V, 10A) blown.
Is the
green LED of indoor unit
flashing?
Is the
red LED of indoor unit flashing
twice?
Are wires
connected properly between
the indoor and the outdoor
units?
Is approx.
DC20V detected between
2/N
-
�
on the outdoor unit terminal
block?
YES
NO
Is approx.
DC20V detected between
�
-
�
on the indoor unit terminal
block?
NO
YES
WAIT
See next page.
Defective outdoor sub
PCB
→
Replace.
Connect properly.
Replace fuse.
Defective indoor control
PCB
→
Replace.
Replace indoor control
PCB.
Defective remote control
→
Replace.
Broken remote control
wire Y
→
Replace.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor sub
PCB
→
Replace.
Defective connection wire
(broken wire)
Noise
Defective indoor control
PCB
→
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Faulty outdoor sub PCB
• Connection between PCB’s
• Blown fuse on single phase
model
• Faulty indoor control PCB
• Defective remote control
• Broken remote control wire
Note: If any anomaly is detected during communication, the error code E5 is displayed. (Outdoor unit red LED flashes twice.) Inspection
procedure is same as above. (Excluding matters related to connection) When the power supply is reset after the occurrence of E5, the
LED will display “
WAIT
”
if the anomaly continues. If the breaker ON/OFF is repeated in a short period of time (within 1 minute),
“
WAIT
”
may be displayed. In such occasion, turn the breaker off and wait for 3 minutes.
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...