400
-
'13 • PAC-T-197
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
–
2-time flash
Stays OFF
Keeps flashing
Content
WAIT
Communication error at
initial operation (3/3)
(Models SRC40-60)
1. Applicable model
5. Troubleshooting
Models SRC40-60
When the remote control
display is extinguished after the
power on.
Diagnosis
Countermeasure
YES
NO
Remote control display is
extinguished after the power on.
NO
NO
NO
NO
YES
Is the
green LED on the indoor unit
flashing?
Is the
fuse on the indoor power
PCB OK?
Is
approx. 10-11V detected
between wires at the remote control
side after disconnecting the
remote control?
Is the
red LED in the outdoor unit flashing
twice?
Are wires
connected properly between the indoor and
the outdoor units?
Is approx.
DC20V detected between -
�
on the outdoor unit terminal
block?
NO
Is approx
DC20V detected between
�
-
�
on the indoor unit terminal
block?
NO
NO
2/N
YES
YES
YES
YES
YES
Replace fuse.
Short-circuit on remote
control wire
Defective remote control
Defective indoor control
PCB
➞
Replace.
Defective remote control
Broken remote control
wire X or Y
Correct wires.
Defective outdoor sub
PCB
➞
Replace.
Defective connection wire
(Broken wire)
Noise
Defective indoor power
PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Connection between PCB’s
• Blown fuse
• Faulty indoor power PCB
• Defective remote control
• Wire breakage on remote
control
• Faulty outdoor sub PCB
Note:
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...