401
-
'13 • PAC-T-197
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
Communication error at
initial operation (1/3)
(Models FDC71-140)
Keeps flashing
Keeps flashing
Stays OFF
2-time flash
1. Applicable model
5. Troubleshooting
Models FDC71-140
Diagnosis
Countermeasure
NO
NO
NO
“ ” is still displayed on the
remote control LED 2 minutes
after power ON.
YES
NO
NO
Is the outdoor
unit control green LED
flashing?
YES
YES
YES
YES
Is the indoor
unit green LED flashing?
Is the outdoor unit
control red LED flashing
twice?
Are wires
connected properly between indoor/
outdoor units?
YES
YES
NO
Is approx.
DC20V detected between
�
-
�
on
the outdoor unit terminal
block?
Is approx.
DC20V detected between
�
-
�
on
the indoor unit terminal
block?
WA IT
To next page
Defective indoor control
PCB
➞
Replace.
Defective indoor control PCB
➞
Replace.
Defective remote control
➞
Replace.
Broken remote control wire Y
➞
Replace.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor control
PCB
➞
Replace.
Defective connection wire
(Broken)
Noise
Defective indoor control or
power PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Faulty indoor control or
power PCB
• Defective remote control
• Broken remote control wire
• Faulty outdoor control PCB
• Broken connection wires
Note:
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...