'13 • PAC-T-197
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
None
No display
Stays OFF
Stays OFF
Stays OFF
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Remote control does not display
anything after the power on.
NO
NO
YES
YES
YES
Is DC10V or
higher detected at remote control connection
terminals?
Is DC10V or higher
detected on remote control wires if
the remote control is
removed?
Are wires
connected properly between the
indoor/outdoor units?
NO
Defective remote control
Defective remote control
Defective connecting wire.
Defective remote control
wire (Short-circuit, etc.)
Defective indoor control
PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Faulty indoor control PCB
• Defective remote control
• Broken remote control wire
Note: