413
-
'13 • PAC-T-197
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E14
Communication error
between master and slave indoor units
Keeps flashing 3-time flash
Keeps flashing
Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it
OK the unit
address setting for master
and slave indoor
units?
NO
YES
Isn’t
the remote
control wiring between
indoor units
defective?
Is it
restored by resetting the
power supply?
Note (1) Set dip switches SW5-1 and SW5-2 as shown in the following table.
(Factory default setting – “Master”)
Master
Slave-a
Slave-b
SW5-1
OFF
OFF
ON
SW5-2
OFF
ON
OFF
Dip
switch
Indoor unit
YES
NO
NO
YES
Correct unit address setting.
Correct wiring.
Defective indoor control
PCB Replace.
• Malfunction by noise
• Check surrounding
environment.
2. Error detection method
When communication error
between master and slave
indoor units occurs
3. Condition of Error displayed
Same as above
4. Presumable cause
• Unit address setting error
• Broken remote control wire
• Defective remote control wire
connection
• Defective indoor control PCB
Note:
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...