416
-
'13 • PAC-T-197
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E19
Indoor unit operation check,
drain motor check setting error
Keeps flashing 1-time flash
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is SW7-1
on the indoor control
PCB ON ?
E19 occurs
when the power ON
NO
YES
Defective indoor control
PCB (Defective SW7)
➞
Replace
Turn SW7-1 on the indoor
control PCB OFF and reset
the power
2. Error detection method
After indoor operation check,
when the communication
between indoor and outdoor
unit is established and SW7-1 is
still kept ON.
3. Condition of Error displayed
Same as above
4. Presumable cause
Mistake in SW7-1 setting
(Due to forgetting to turn OFF
SW7-1 after indoor operation
check)
Note: