433
-
'13 • PAC-T-197
E47
1. Applicable model
5. Troubleshooting
Model FDC71
Diagnosis
Countermeasure
YES
NO
NO
Is the
Power supply
voltage OK?
Is the
checked results of
insulation resistance and
coil resistance (1) of
compressor motor
OK?
(1) 1.154
Ω
or more at 20°C
YES
Check power supply.
Replace compressor.
Defective outdoor Inverter
PCB
➞
Replace.
2. Error detection method
In order to prevent from
overcurrent of A/F, if the current
exceeds the specifications, it
makes the compressor stopping.
3. Condition of error displayed
•
If the output current of A/F
exceeds the specifications,
it makes the compressor
stopping.
4. Presumable cause
• Defective inverter PCB
Note:
Error code
Remote control:
LED
Green
Red
Outdoor control PCB
Outdoor Inverter
PCB
1-time flash
Keeps flashing
Yellow LED
Indoor
Stays off
Keeps flashing
Content
7-time flashing
Inverter
PCB A/F module anomaly
(Model FDC71VNX)