-
447
-
'13 • PAC-T-197
Error code
Remote control:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
5-time flash
Keeps flashing
Indoor control PCB
Stays OFF
Keeps flashing
Content
Stays OFF
Yellow LED
E59
1. Applicable model
5. Troubleshooting
Models FDC71-140
Diagnosis
Countermeasure
NO
Is the
power transistor
module OK?
(inverter PCB anomaly)
NO
Is the
inverter output OK?
(Check by inverter
checker)
Does it start?
NO
YES
YES
YES
Note(1) Several times restarting
may recover it, because liquid
refrigerant migrated in the
compressor could be discharged
from the compressor.
After power OFF, turn SW10-4 of
inverter PCB ON and connect the
inverter checker. Then power ON
again.
Try to restart several times
From previous page
Replace inverter PCB
Replace inverter PCB
Replace compressor
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note:
Compressor startup failure (2/2)
(Models FDC71-140)
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...