456
-
None
Power supply system error
(Power supply to indoor control PCB)
–
–
Stays OFF
2-time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
AC220/240V
detected between 1 and
2 on the terminal block
of indoor
unit?
NO
NO
Are fuse OK
(250V 3.15A)?
YES
YES
NO
Is
AC380/415V
for 3-phase unit detected
between 1, 2 and 3 on the teminal
block of outdoor unit or is AC220/240V
for 1-phase unit detected between
1 and 2 on the terminal
block of outdoor
unit?
YES
Defective outdoor control
PCB (Noise filter)
Misconnection or breakage
of connecting wires
Replace fuse.
Defective indoor control
PCB
➞
Replace.
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty indoor control PCB
• Broken harness
• Faulty outdoor control PCB
(Noise filter)
Note: