-
464
-
None
No display
–
–
Stays OFF Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Remote control does not display
anything after the power on.
NO
NO
YES
YES
Is DC10V or
higher detected at remote control connection
terminals?
Is DC10V or higher
detected on remote control wires if
the remote control is
removed?
NO
NO
YES
YES
YES
Is DC10V or
higher detected at interface kit connection
terminals?
Is DC10V or higher
detected on connecting wires if
the interface kit is
removed?
Are wires
connected properly between the
indoor/outdoor units?
NO
Defective remote control
Defective remote control
Defective interface kit
Defective interface kit
Defective connecting wire.
Defective remote control
wire (Short-circuit, etc.)
Defective indoor control
PCB
➞
Replace.
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
• Faulty indoor control PCB
• Defective remote control
• Broken remote control wire
• Defective interface kit
Note:
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor
control PCB
Content
-
464
-
'13 • PAC-T-197
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...