467
-
E6
Indoor heat exchanger
temperature sensor anomaly
1(3)-time flash
(1)
ON
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the
connection of indoor heat
exchanger temperature sensor
connector OK?
Are
characteristics of indoor
heat exchanger temperature
sensor OK?
YES
Temperature-resistance characteristic
Te
mperature sensor resistance (k
Ω
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
(Broken wire)
(Short circuit)
5k
Ω
at 25
°C
Correct.
➞
Insert connector
securely.
Defective indoor heat
exchanger temperature
sensor
➞
Replace.
Defective indoor control
PCB
➞
Replace.
(Defective indoor unit heat
exchanger temperature
sensor input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger sensor (Th2
1
, Th2
2
).
3.
Condition of Error displayed
• When the temperature sensor
detects -28
°C or lower for 15
seconds continuously, the
compressor stops. After 3-
minutes delay, the compressor
starts again automatically,
but if this error occurs again
within 60 minutes after the
initial detection.
4. Presumable cause
• Defective indoor heat
exchanger sensor connector
• Indoor heat exchanger
temperature sensor anomaly
• Faulty indoor control PCB
Note:
Note(1) Value in ( ) are the Th2
2
.
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor
control PCB
Content
-
467
-
'13 • PAC-T-197
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...