Error code
Remote control:
Content
1-time flash
Keeps flashing
1-time flash
1-time flash
ON
Indoor display
RUN light
TIMER light
Green LED
Yellow LED
Red LED
Outdoor
control PCB
Outdoor
inverter PCB
E42
Current cut (1/2)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
Power supply
voltage OK?
YES
Are the
service valves
opened?
NO
YES
Is the
high pressure
during operation
OK?
YES
Is the
checked result of
insulation resistance and
coil resistance (1) of
compressor motor
OK?
YES
(1) 0.293
Ω
or more at 20°C (Single phase models)
1.172
Ω
or more at 20°C (3-phase models)
NO
NO
NO
To next page.
Check power supply.
Open the valves.
Check refrigerant amount
and refregerant circuit
* In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because liquid
refrigerant (migrated)
in the compresser is
discharged from the
compressor.
Replace compressor.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3.
Condition of Error displayed
•
If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
•
After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minute after the intial
detection.
4. Presumable cause
• The valves closed
• Faulty power supply
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
-
480
-
'13 • PAC-T-197
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...