E59
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
Is the
power transistor
module OK?
(inverter PCB anomaly)
NO
Is the
inverter output OK?
(Check by inverter
checker)
Does it start?
NO
YES
YES
YES
Note(1) Several times restarting
may recover it, because liquid
refrigerant migrated in the
compressor could be discharged
from the compressor.
After power OFF, turn SW10-4 of
inverter PCB ON and connect the
inverter checker. Then power ON
again.
Try to restart several times
From previous page
Replace inverter PCB
Replace inverter PCB
Replace compressor
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
Note:
Error code
Remote control:
Content
5-time flash
Keeps flashing
Stays OFF
–
–
Indoor display
RUN light
TIMER light
Green LED
Yellow LED
Red LED
Outdoor
control PCB
Outdoor
inverter PCB
Compressor startup failure (2/2)
-
491
-
'13 • PAC-T-197