548
-
'13 • PAC-T-197
Model
Item
FDC140VNX
Power source
1 Phase 220-240V 50Hz / 220V 60Hz
Operation
data
Nominal cooling capacity (range)
kW
14.0 [ 5.0(Min.)~ 16.0(Max.)]
Nominal heating capacity (range)
kW
16.0 [ 4.0(Min.)~ 18.0(Max.)]
Sound power level
Cooling
dB(A)
72
Heating
Sound pressure level
Cooling
49
Heating
52
Silent mode sound pressure level
—
Exterior dimensions (Height x Width x Depth)
mm
1300×970×370
Exterior appearance
( Munsell color )
Stucco White
( 4.2Y7.5/1.1 ) near equivalent
Net weight
kg
105
Compressor type & Q'ty
RMT5134MDE2×1
Compressor motor (Starting method)
kW
Direct line start
Refrigerant oil (Amount, type)
0.9 M-MA68
Refrigerant (Type, amount, pre-charge length)
kg
R410A 4.5kg in outdoor unit (incl. the amount for the piping of : 30m)
Heat exchanger
M shape fin & inner grooved tubing
Refrigerant control
Electronic expansion valve
Fan type & Q'ty
Propeller fan ×2
Fan motor (Starting method)
W
86 x 2 < Direct line start >
Air flow
Cooling
m
3
/min
100
Heating
Shock & vibration absorber
Rubber sleeve(for compressor )
Electric heater
W
20(Crank case heater)
Safety equipments
Internal thermostat for fan motor.
Abnormal discharge temperature protection.
Installation
data
Refrigerant piping size ( O.D. )
mm
Liquid line:
φ
9.52 (3/8")
Gas line:
φ
15.88 (5/8")
Connecting method
Flare piping
Attached length of piping
m
—
Insulation for piping
Necessary (both Liquid & Gas lines)
Refrigerant line (one way) length
m
Max.100m
Vertical height diff. between O.U. and I.U.
m
Max.30m
(Outdoor unit is higher)
Max.15m
(Outdoor unit is lower)
Drain hose
Holes size
φ
20 x 3pcs
IP number
IP24
Standard accessories
Edging
Option parts
—
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these value are somewhat
higher due to ambient conditions.
(4) The operation data indicate when the air-conditioner is operated at 230V50Hz or 220V60Hz.
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO5151-T1
Heating
20˚C
—
7˚C
6˚C
D
PJF000Z315
The pipe length is 7.5m.
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...