552
-
'13 • PAC-T-197
[Example]
(Conditions) Operation Voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC125VSX × 1 unit
Indoor unit: FDT50VF × 1 unit, FDT71VF1 × 1 unit
Item
Model
FDC125VSX
FDT50VF
FDT71VF1
Operation characteristics of each unit
(Cooling/Heating)
Power consumption (kW)
Running current (A)
0.04/0.04
0.20/0.20
3.11/3.26
7.9/8.2
0.08/0.08
0.40/0.40
Ԙ
Total power consumption (kW)
(Cooling) 3.11 + 0.04 + 0.08 = 3.23 (kW)
(Heating) 3.26 + 0.04 + 0.08 = 3.38 (kW)
ԙ
Total running current (A)
(Cooling) 7.9 +
[
(0.20 + 0.40) × )
]
= 8.1 (A)
(Heating) 8.2 +
[
(0.20 + 0.40) × )
]
= 8.4 (A)
3
1
..
..
Ԛ
Total power factor (%)
(Cooling) × 100 = 61 %
(Heating) × 100 = 61 %
3.23 × 1000
3 × 8.1 × 380
..
..
3.38 × 1000
3 × 8.4 × 380
3
1