564
-
'13 • PAC-T-197
Installation of the control holder
Caution
DO NOT install it on the following places
1) Places exposed to direct sunlight
2) Places near heat devices
3) High humidity places
4) Hot surface or cold surface enough to generate
condensation
5) Places exposed to oil mist or steam directly
6) Uneven surface
Installation tips for the remote control holder
• Adjust and keep the holder upright.
• Tighten the screw to the end to avoid scratching
the remote control.
• DO NOT attach the holder to plaster wall.
①
Detach the back lid.
②
Insert the batteries. (two AAA batteries)
③
Reattach the back lid.
●
After safety con rmation, turn on the power.
●
Transmit a cooling operation command with wireless remote control, while the backup
button on the receiver is pressed.
●
If the backup button on the receiver is pressed during a test run, it will end the test run.
●
If you cannot operate the unit properly during a test run, please check by consulting with
inspection guides on the wiring diagram of outdoor units.
Wood screw
Holder for
remote
control
This setting is to avoid the mixed communication with other household electric
appliances or the mixed communication when two receivers are located closely.
①
Setting change of the wireless remote control
Pressing ACL and AIRFLOW button at the same time or inserting the batteries
with pressing AIRFLOW button will customize the signal.
Note
*When the batteries are removed, the setting will return to the default setting.
Make sure to reset it when the batteries are replaced.
②
Setting the PCB of the receiver
Turn SW1-1 off.
Do both procedures
①
and
②
.
●
Wireless remote control
Setting to
avoid mixed
communication.
●
PCB of the receiver
SW1-4
(Auto restart)
SW1-1
(Customized signal
setting to avoid
mixed communication)
SW1-2
(Receiver master/slave
setting)
SW1-1
Customized signal setting to
avoid mixed communication
ON
: Normal
OFF : Remote
SW1-2
Receiver master/slave setting
ON
: Master
OFF : Slave
SW1-4
Auto restart
ON
: Valid
OFF : Invalid
: Default setting
Up to 16 indoor units can be connected.
①
Connect the XY terminal with 2-core wire.
As for the size, refer to the following note.
②
For Packaged air conditioner series, set the
indoor unit address with SW2 on the indoor
unit PCB from [0] to [F] so as not to duplicate.
③
For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the
indoor unit PCB from [000] to [127] so as not to duplicate.
KIT
Restrictions on the thickness and length of wire
(Maximun total extension 600m.)
Within 100m x 0.3 mm
2
Within 200m x 0.5 mm
2
Within 300m x 0.75mm
2
Within 400m x 1.25mm
2
Within 600m x 2.0 mm
2
Standard
Terminal block
Remote control
Indoor unit (1)
Address (0)
Indoor unit (2)
Address (1)
Indoor unit (16)
Address (F)
Up to two receivers can be installed in one indoor unit group.
Switch
Setting
Function
SW1-2
ON
Master
OFF
Slave
Indoor unit
RCN-KIT
SW1[Master]
RCN-KIT
SW1[Slave]
Remote control line
(Non-polarized)
④
Remote control
How to insert batteries
⑤
Cooling test run operation
(A) Methods of avoiding the malfunction due to the mixed communication
(B) Control plural indoor units with one remote control
(C) Master/Slave setting when using plural remote control
⑥
Setting of wireless remote control and receiver
CHECK MODE
ON/
OFF
CHECK
FILTER
CHECK
TIMER RUN/
CHECK
Back-up button
(D) Change setting of auto mode operation
Auto mode operation is prohibited to be selected for KX models (except for KXR
models).
Therefore be sure to change setting of remote control to disable the auto mode
operation for these models according to the following procedure.
While pressing the MODE button, press the ACL switch, or while pressing the
MODE button, insert the batteries to the remote control. Then the auto mode
can be invalid.
Attention
When the batteries are removed, it is returned to initial setting (Auto mode
becomes valid).
Accordingly when replacing the batteries, be sure to perform the above operation
once again.
(E) Change setting of fan speed
While pressing the FAN SPEED button, press the ACL switch, or while pressing
the FAN SPEED button, insert the batteries to the remote control. Then the
fan speed can be changed from 2-speed setting to 3-speed setting.
When changing fan speed setting of remote control, be sure to perform the same
fan speed setting as that of the indoor unit model to be used.
Attention
When the batteries are removed, it is returned to initial setting (Fan speed setting
is 2-speed).
Accordingly when replacing the batteries, be sure to perform the above operation
once again.
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...