329
-
'13 • PAC-T-197
(c) In case of anomaly
a) If any anomaly occurs on a unit in a group (a protective function operates), that unit stops with the anomalous
stop but any other normal units continue to run as they are.
b) Signal wiring procedure
Signal wiring between indoor and outdoor units should be made on each unit same as the normal wiring. For
the group control, lay connect with sires wiring between rooms using terminal blocks (X, Y) of interface kit.
Connect the remote control communication wire separately from the power supply wire or wires of other
electric devices (AC220V or higher).
(10) Filter sign
As the operation time (Total ON time of ON/OFF switch) accumulates to 180 hours (1), “Filter cleaning” is displayed on the
remote control. (This is displayed when the unit is in trouble and under the centralized control, regardless of ON/OFF)
Note (1) Time setting for the filter sign can be made as shown below using the indoor function of wired remote control “FILTER SIGN SET”. (It is set at 1 at the
shipping from factory.)
Filter sign setting
Function
Setting 1
Setting time: 180 hrs (Factory default)
Setting 2
Setting time: 600 hrs
Setting 3
Setting time: 1,000 hrs
Setting 4
Setting time: 1,000 hrs (Unit stop)
(2)
(2) After the setting time has elapsed, the “FILTER CLEANING” is displayed and, after operating for 24 hours further (counted also during the stop), the unit
stops.
(11) Outline of automatic operation
(a)
Determination of operation mode
The unit checks the indoor air temperature and the outdoor air temperature, determines the operation mode, and then
begins in the automatic operation.
(b)
The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the previous
operation mode, changes the operation mode.
(i)
If the setting temperature is changed with the remote control, the operation mode is judged immediately.
(ii)
When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending
on the difference between the setting temperature and the indoor air temperature.
(iii)
When the operation mode has been judged following the change of setting temperature with the remote control, the
hourly judgment of operation mode is cancelled.
(c)
When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is
selected during heating or cooling operation, the unit is operated in the previous operation mode.
(12) Frost prevention control
(a) Operating conditions
(i)
More than 8 minutes after starting the compressor.
(ii)
Indoor heat exchanger temperature (detected with Th2) is lower than 2.5
℃
.
(b) Contents of frosting operation
During this control
Reset
Compressor ON/OFF command
Forced stop
Operation command
Indoor fan motor
Depending on the airflow setting with the remote
controller
(c) Resetting condition: Indoor heat exchanger temperature (Th2) is higher than 8
℃
.
27.5
19.5
18
Heating
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
A
Indoor heat exchanger temperature (
℃
)
2.5
8
During
control
Reset
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...