332
-
'13 • PAC-T-197
(2) Cooling overload protective control
(a) Operating conditions:
(b) Detail of operation
(c) Reset conditions:
Outdoor air temperature
Lower limit speed
40
41
46
47
OFF
ON1
ON2
Outdoor air temperature ( )
C
º
1)
2)
(3) Cooling high pressure control
(a) Purpose:
Prevents anomalous high pressure operation during cooling.
(b) Detector:
Outdoor heat exchanger sensor (TH1)
(c) Detail of operation:
A
B
C
Outdoor heat exchanger temperature (°C)
8rps
(1)
8rps
(1)
0rps
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
lower limit
speed 30 rps
(Example) Fuzzy
Notes (1) When the outdoor heat exchanger temperature is in the range of A~CºC, the speed is reduced by 8 rps at each 20 seconds.
(2) When the temperature is 63ºC or higher, the compressor is stopped.
(3) When the outdoor heat exchanger temperature is in the range of A~CºC, if the compressor command speed is been maintained and the operation has
continued for more than 20 seconds at the same speed, it returns to the normal cooling operation.
(4) Cooling low outdoor temperature protective control
(a) Operating conditions:
When the outdoor air temperature (TH2) is CºC or lower continues for 20 seconds while the
compressor command speed is other than 0 rps.
(b) Detail of operation:
1) The lower limit of the compressor command speed is set to 45 (35) rps and even if the speed becomes lower than
45 (35) rps, the speed is kept to 45 (35) rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
2) The upper limit of the compressor command speed is set to 60 (75) rps and even if the calculated result becomes
higher than that after fuzzy calculation, the speed is kept to 60 (75) rps.
Note (1) Values in ( ) are for outdoor air temperature is CºC
Outdoor air temperature(TH2)
A
B
C
TH2 >= 32ºC
53
58
63
TH2 < 32ºC
51
53
56
C
D
A
B
OFF
Upper limit 60 rps
Lower limit 45 rps
ON
ON
Upper limit 75 rps
Lower limit 35 rps
Outdoor air temperature (°C)
First time
Since the seconds
times
9
A
Outdoor air temp. (˚C)
B
C
D
11
22
25
16
19
25
28
¡
Values of A, B, C, D
(c) Reset conditions:
When either of the following condition is satisfied.
1) The outdoor air temperature (TH2) is D ºC or higher.
2) The compressor command speed is 0 rps.
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...