333
-
'13 • PAC-T-197
(5) Heating high pressure control
(a) Start condition :
When the indoor heart exchanger temperature (ThI-R) has risen to a specified temperature while the
compressor is turned on.
(b) Compressor command speed is controlled according to the zones of indoor heat exchanger tempera-
ture as shown by the following table.
(6) Heating overload protective control
ThI-R<P1
P1
≦
ThI-R<P2 P2
≦
ThI-R<P3
P3
≦
ThI-R
Protection control speed (NP)
Normal
Retention
NP-4rps
NP-8rps
Sampling time (s)
Normal
10
10
10
(a)
Operating conditions :
(b) Detail of operation
H
13
90(75)rps
30(40)rps
30(40)rps
than that after fuzzy calulation, the speed is kept to 30(40)rps. However, when the thermo becomes OFF, the
㩿㫀㪀
㩿㫀㫀㪀
㩿㫀㫀㫀㪀
speed is
Note (1) Values in ( ) are for outdoor air temperature at 17ºC.
Reset conditions:
11
H
11
13
16
17
OFF
Upper 75rps
Lower 40rps
Upper 90rps
Lower 30rps
Outdoor air temperature(ºC)
(c)
ThI-R
NP
P1
P2
P3
NP<50
45
52
54.5
50
≦
NP<115
45
52
57
115
≦
NP<120
45-43
52-50
57-55
120
≦
NP
43
50
55
Unit:°C
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...