337
-
'13 • PAC-T-197
(a) Cooling/dehumidifying operation
Unit: rps
Model
71
100
125
140
Max. required
frequency
Usual operation
88
75
95(92)
95(92)
Silent mode, outdoor temperature
≦
15°C
80
50
60
70
Min. required frequency
20
20
20
20
Note (1) Value in ( ) are for the 3 phase models.
(b) Heating operation
Unit: rps
Model
71
100
125
140
Max. required
frequency
Usual operation
112
100
120
120
Silent mode
90
60
70
70
Min. required frequency
20
20
20
20
(c) If the indoor unit fan speed becomes “Me” or “Lo”, Max required frequency goes down
accordingly depending on indoor unit model.
(d) Max. required frequency under high outdoor air temperature in cooling mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Unit: rps
Model
71
100
125
140
Max. required
frequency
Outdoor air temperature is
40°C or higher
76
75
75
75
Outdoor air temperature is
46°C or higher
62
70
70
70
(e) Max. required frequency under outdoor air temperature in heating mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Unit: rps
Model
71
100
125
140
Max. required
frequency
Outdoor air temperature is
18°C or higher
76
75
80
85
(f) Selection of max. required frequency by heat exchanger temperature
(i) Maximum required frequency is selected according to the outdoor unit heat exchanger temperature (Tho-R) during
cooling/dehumidifying or according to the indoor unit heat exchanger temperature (ThI-R) during heating mode.
(ii) When there are 3 indoor unit heat exchanger temperatures (ThI-R), whichever the highest applies,
Unit: rps
Model
71
100
125
140
Max. required
frequency
Cooling/
dehumidifying
Outdoor unit heat exchanger
temperature is 56(61)°C or higher
60
75
95
〔
92
〕
95
〔
92
〕
Heating
Indoor unit heat exchanger
temperature is 56(61)°C or higher
60
100
100
100
Note (1) Value in ( ) are for the 71 model.
(2) Value in
〔
〕
are for the 3 phase models.
(g) When any of the controls from (a) to (f) above may duplicate, whichever the smallest value among duplicated controls is
taken as the maximum required frequency.
(h) During heating, it is operated with the maximum required frequency until the indoor unit heat exchanger temperature
becomes 40°C or higher.
(a) Compressor starts upon receipt of the thermostat ON signal from the indoor unit.
(b) However, at initial start after turning the power supply breaker, it may enter the standby state for maximum 30 minutes
(“ PREPARATION” is displayed on the remote control) in order to prevent the oil loss in the compressor.
If the cooling/dehumidifying/heating operation is selected from the remote control when the outdoor unit is in the standby
state, “ PREPARATION” is displayed for 3 seconds on the remote control.
(
Ⅱ
) Models FDC71-140
(1) Determination of compressor speed (frequency)
Required frequency
(2) Compressor start control
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...