(4) Outdoor unit fan control
(a) Outdoor unit fan tap and fan motor speed
Unit: min
-1
Model
Mode
Fan motor tap
71
➀
speed
➁
speed
➂
speed
➃
speed
➄
speed
➅
speed
➆
speed
Cooling/Dehumidifying
200
400
600
710
810
850
950
Heating
200
400
600
710
810
850
950
100
➀
speed
➁
speed
➂
speed
➃
speed
➄
speed
➅
speed
➆
speed
Cooling/Dehumidifying
200
370
560
640
745
870
910
Heating
200
370
560
650
830
870
910
125, 140
➀
speed
➁
speed
➂
speed
➃
speed
➄
speed
➅
speed
➆
speed
Cooling/Dehumidifying
200
370
560
640
745
870
910
Heating
200
370
560
650
830
870
910
(b) Fan tap control during Cooling/Defumidifying operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the higher.
• Silent mode only
zone
zone
zone
zone
zone
zone
zone
zone
zone
Tap 5(6)
Tap 5(6)
Tap 5(6)
Tap 4
zone
Tap 5
Tap 5
Tap 5
Tap 4
zone
Tap 5(6)
Tap 5(6)
Tap 4(6)
Tap 3
zone
Tap 5
Tap 5
Tap 3
Tap 3
zone
Tap 4
Tap 4
Tap 3
Tap 2
zone
Tap 4
Tap 3
Tap 3
Tap 2
zone
Tap 3
Tap 3
Tap 2
Tap 1
zone
Tap 3
Tap 3
Tap 2
Tap 1
Note (1) Value in ( ) are for the model 71.
zone
zone
Outdoor air temp. (˚C)
15
18
zone
30
37
zone
46
48
zone
Outdoor unit heat exchanger temp. (˚C)
20
30
zone
33
40
zone
43
53
zone
(c) Fan tap control during heating operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the lower.
• Silent mode only
zone
zone
zone
zone
zone
zone
zone
Tap 3
Tap 3
Tap 4
zone
Tap 3
Tap 3
Tap 3
zone
Tap 3
Tap 4(5)
Tap 5
zone
Tap 3
Tap 3
Tap 5
zone
Tap 4
Tap 5
Tap 6
zone
Tap 4
Tap 5
Tap 6
Note (1) Value in ( ) is for the model 71.
3
9
12
15
-2
0
1
3
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
zone
zone
zone
zone
zone
zone
(d) Outdoor unit fan control at cooling low outdoor air
(i) When all the following conditions are established after the start of compressor, the following control is implemented.
If the outdoor air temperature (Tho-A) is in the zone in the cooling/dehumidifying mode, it has elapsed 20
seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is
controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
Note (1) It is detected with Tho-R1 or R2, whichever the higher.
5
10
Retained
Outdoor unit fan speed
-10min
-1
20
30
Outdoor unit fan speed
+10min
-1
zone
zone
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
Summary of Contents for V Multi 100VNX
Page 98: ... 97 13 PAC T 197 Models FDT100VF1 125VF 140VF H H H H H C B A F G D G PJF000Z285 A ...
Page 101: ... 100 13 PAC T 197 Models FDEN60VF 71VF1 C2 C1 A B A B D C1 C2 C1 C2 E G F C PFA003Z817 ...
Page 116: ... 115 13 PAC T 197 b Wireless remote control RCN E1R 60 17 150 Unit mm ...
Page 291: ... 290 13 PAC T 197 261 12 PAC T 173 ー K ...
Page 590: ... 589 13 PAC T 197 3 8 SUPER LINK E BOARD SC ADNA E F ...
Page 591: ... 590 13 PAC T 197 ...