(10) Base heater ON/OFF output control (option)
(i) Base heater ON conditions
When all of following conditions are met, the base heater is turned ON.
・
Outdoor air temperature (detected with Tho-A) is 3ºC or lower.
・
In the heating mode
・
When the compressor is turned ON
(ii) Base heater OFF conditions
When either one of following conditions is met, the base heater is turned OFF.
・
Outdoor air temperature (detected with Tho-A) is 5ºC or higher.
・
When the compressor stop has been detected for 30 minutes continuously
・
In the cooling or dehumidifying mode
Base heater ON
Base heater OFF
Outdoor air temperature (ºC) [Tho-A]
5
3