2-7 

 

 

B)    Input Contacts (for remote access of UPS) 

 

External contacts are provided by the user of the UPS system. The terminal voltage at the 

UPS is 24Vdc. External dry contacts are to be provided accordingly.   

 

NOTE:

 

  Do not apply voltages to remote access input terminals. Damage to UPS may result. 

 

Refer to Figure 2.8 for a typical wiring configuration. Although this figure shows the 

emergency stop configuration, the same wiring arrangement is used for battery 

temperature high. See below for terminal connection details. 

 

FIGURE 2.8

    Remote "Stop" Contact Connections   

 

 

 

 

 

 

 

 

 

 

 

 

 

Details of input contacts for remote access :

 

 

Terminals 1 to 2 

“Emergency Stop” contact input

 

Used to perform a remote UPS emergency power off (EPO). 

The load will be dropped. 

Terminals 3 to 4 

“Battery Temp. High” contact input

 

Input fed by a thermocouple that monitors battery temperature. The converter 

float voltage level is reduced for battery over-temperature conditions. The 

external thermocouple will be user supplied 

 

NOTE :

 In all cases, a switch having a protective cover is recommended in order to reduce 

possibility of accidental operation.   

 

User supplied

 

 

Relay Coil current : 8.3mA

Use Momentary Switches 

UPS Cabinet   

External to UPS 
Cabinet 

Relay 

 

Coil 

24 VDC

Emergency

Stop

2

Summary of Contents for 2033C SERIES

Page 1: ...Revision 2 1 November 11 2003 ALN H0626 MITSUBISHI ELECTRIC AUTOMATION INC UNINTERRUPTIBLE POWER SUPPLY SYSTEM 2033C SERIES OWNERS TECHNICAL MANUAL...

Page 2: ...MITSUBISHI ELECTRIC 2033C SERIES UPS OWNERS TECHNICAL MANUAL Page Number i MITSUBISHI ELECTRIC 2033C SERIES UPS Preface...

Page 3: ...OLS AND INDICATORS 2 1 2 1 LCD TOUCH PANEL MONITOR DISPLAY AND KEYPAD 2 1 2 2 EXTERNAL SIGNAL TERMINAL BLOCK 2 5 2 3 EXTERNAL COMMUNICATION CONNECTOR 2 8 3 0 INSTALLATION AND OPERATION 3 1 3 1 TRANSPO...

Page 4: ...Table 1 2 UPS Module Information 1 14 Table 1 3 Detail of Specifications 1 15 Table 1 4 Rating of Conductor and Fuses 1 16 Table 3 1 How to Transport and Install the System 3 1 Table 3 2 List of UPS W...

Page 5: ...2 1 11 Figure 1 7 External I F PCB RYDR X 1 11 Figure 1 8 Main Control PCB UPFR K 1 12 Figure 2 1 Operation Display Panel 2 1 Figure 2 2 MAIN MENU Screen 2 2 Figure 2 3 MEASURMENT Screens 2 2 Figure 2...

Page 6: ...f this manual Warning A warning notice icon conveys information provided to protect the user and service personnel against hazards and or possible equipment damage Caution A caution notice icon convey...

Page 7: ...descriptions for the installation and operation procedures of the UPS Please read this manual carefully and retain it for future reference This manual contains important instructions for the 2033C Se...

Page 8: ...The AC input circuit breaker MCCB is to be field supplied and installed Circuit breaker MCCB specifications are as follows Capacity kVA AC input Voltage Vac AC input Rating Aac Recommended Breaker A...

Page 9: ...own of equipment supported by the UPS The UPS is simple to start up operate and maintain The 2033C Series UPS is available in seven 7 kVA sizes 7 5 10 15 20 30 40 and 50kVA Specifications for each kVA...

Page 10: ...UPS components which contain the equipment and controls necessary to convert input AC power to regulated DC power required for battery charging and for supplying power to the Inverter INVERTER The UP...

Page 11: ...eferring to Figure 1 1 Input AC power is converted to DC by the Converter DC power is utilized to charge the UPS battery and to provide power to the Inverter The Inverter converts the DC power to clea...

Page 12: ...r to the load A fully charged battery will provide power for the specified time at the rated load or longer at reduced load When power is restored after a low battery shutdown the Converter automatica...

Page 13: ...e bypass switch is shown as 52CS in Figure 1 4 52CS is a two position three point make before break transfer switch 30 40 50kVA Two contactors 52MB 52L are used instead of the 52CS A rotary switch SWM...

Page 14: ...nce bypass 1 On the front panel press the STOP button The BYP OP LED illuminates within 3 seconds 2 After confirming that the BYP OP LED is illuminated Rotate MBS 52CS SWM clockwise to the TRANSFER po...

Page 15: ...e Number 1 9 FIGURE 1 5a UPS Parts Location 7 5 20kVA 4 Main PCB UPFR K 3 Relay PCB RYDR X UPS module FRONT VIEW 7 Maintenance bypass transfer switch 52CS Battery 5 AC input AC output terminal Cooling...

Page 16: ...age Number 1 10 FIGURE 1 5b UPS Parts Location 30kVA 4 Main PCB UPFR K 3 Relay PCB RYDR X UPS module FRONT VIEW 7 Maintenance bypass transfer switch SWM Battery 5 AC input AC output terminal Cooling f...

Page 17: ...rnal I F PCB RYDR X DPAU 57 DPAU 72 8 SW5 TEST switch RYDR X 10 CN62 RS232C D sub Connector 9 External contact signal terminal block 11 CN64 RS232C D sub Connector 4 Main PCB UPFR K UPS module FRONT V...

Page 18: ...ay screens 2 Display PCB DPAU 72 Switches on DPAU 72 board FOR SERVICE PERSONNEL ONLY Figure 1 6 8 SW5 TEST switch 3 Relay PCB RYDR X board Signal I F on RYDR X board Figure 1 7 9 External contact sig...

Page 19: ...be operated by personnel other than an Authorized Service Engineer 9 External contact signal terminal block Terminal block to connect contact signal input output lines to and from external dry contac...

Page 20: ...15kVA 12kW 20kVA 16kW 30kVA 24kW 40kVA 32kW 50kVA 40kW 208 208 208 208 208 208 208 208 208 208 208 208 208 208 TABLE 1 2 UPS Module Information UPS kVA CABLE ENTRY WIDTH in mm DEPTH in mm HEIGHT in mm...

Page 21: ...wer Factor 0 8 nominal Power Factor range 0 8 1 0 lagging within output kW rating Voltage THD 2 typical THD at 100 Linear Load 4 typical THD at 100 non linear load Transient Response 3 typical at 100...

Page 22: ...0A 150A CB2 DC Input Contactor 60A 100A 150A 150A CB3 Static Bypass Input Contactor 60A 100A 150A 150A 52C AC Output Contactor 60A 100A 150A 150A FIU W AC Input Fuse 140A 660V 180A 600V 280A 660V 280A...

Page 23: ...ouch Panel Monitor Display The Liquid Crystal Display LCD Touch panel Monitor Display indicates power flow measured values and fault and error messages via user selectable display screens MAIN MENU SC...

Page 24: ...n in Figure 2 3 FIGURE 2 3 MEASUREMENT Screens Each MEASUREMENT Screen includes a MAIN Menu Screen Touch Icon On pressing this MAIN Touch icon the display returns to the MAIN MENU Screen AC Output Mea...

Page 25: ...as fault alarm History can be displayed as shown in Figure 2 4 The FAULT DISPLAY Touch icon will flash on the MAIN MENU Screen if there are Fault Alarms that have not been restored Pressing the DETAI...

Page 26: ...Illuminated when power is supplied to load devices by static bypass 5 UPS failure FAILURE red Illuminated when UPS is in fault mode 6 Inverter start START green Inverter start button When pressed the...

Page 27: ...UPS functions Layout of terminals is shown in Figure 2 6 with a functional description of the input output port presented FIGURE 2 6 External Signal Terminal Block NEC Class2 TB BATTERY TEMP HIGH Opti...

Page 28: ...when a fault alarm occurs Terminals 7 to 8 Load on Inverter contact Activated when the power is supplied by the inverter Terminals 9 to 10 Load on Bypass contact Activated when the power is supplied b...

Page 29: ...rature high See below for terminal connection details FIGURE 2 8 Remote Stop Contact Connections Details of input contacts for remote access Terminals 1 to 2 Emergency Stop contact input Used to perfo...

Page 30: ...ctor is shown in Figure 2 9 FIGURE 2 9 External communication connector NEC Class2 Pin 1 Not used Pin 2 RXD Receive data Pin 3 TXD Transmit data Pin 4 DTR Always high level Pin 5 GND Signal ground Pin...

Page 31: ...UPS cabinet as shown in Figure 3 1 Fix the UPS unit in place using the four 4 leveling feet Note Do not transport in a horizontal position Cabinets should be maintained upright within 15 of the vertic...

Page 32: ...side 7 8 200 mm Top side 39 4 1000 mm C Space requirement for routine maintenance Allow for the following space at the time of installation Front 39 4 1000 mm Sides 1 0 25 mm Rear 7 8 200 mm D Battery...

Page 33: ...cedure for Cable Connections Refer to Table 3 4 for cable sizes I Confirm the capacity of the UPS being installed Identify the input output power terminal blocks as shown in the appropriate Figure 3 2...

Page 34: ...ger 180 in lbs 20kVA 208V 6 AWG or larger 180 in lbs 6 AWG or larger 180 in lbs 30kVA 208V 2 AWG or larger 180 in lbs 2 AWG or larger 180 in lbs 40kVA 208V 2 0 AWG or larger 180 in lbs 2 0 AWG or larg...

Page 35: ...BISHI ELECTRIC 2033C SERIES UPS Fig 3 2 UPS Terminal Designation Terminals INPUT A B C N Terminals OUTPUT A B C N Output AC input BATTERY CB3 Static Transfer Switch 52C CB1 FO FI CONVERTER INVERTER UP...

Page 36: ...ERIES UPS FIGURE 3 3 Input Output Power Terminals 7 5kvA 20kVA ALL POWER TERMINALS USE 1 4 6 MM DIAMETER BOLTS Control printed circuit boards Fan Inverter and Converter 52CS Input Output Power Termina...

Page 37: ...utput Power Terminals 30kVA Converter Inverter Unit Cooling fan A B C N A B C N Battery Battery Battery Battery RYDR X N P INPUT OUTPUT TRANSFER NORMAL BYPASS MBS DC INPUT Control printed circuit boar...

Page 38: ...2033C SERIES UPS FIGURE 3 5 Input Output Power Terminals 40kvA 50kVA A B C N A B C N N P AC INPUT AC OUTPUT DC INPUT Grounding bar MBS BYPASS TRANSFER NORMAL RYDR X Control printed circuit boards Conv...

Page 39: ...n figure 3 6 Press the CLEAR button If code 99 is indicated on the FAULT DISPLAY Screen press CLEAR button again FIGURE 3 6 EPO button EPO On position Normal position B UPS Shutdown Procedure 1 If a t...

Page 40: ...ront panel press the STOP button The BYP OP LED illuminates within 3 seconds 2 After confirming that the BYP OP LED is illuminated Rotate the MBS 52CS SWM clockwise to the TRANSFER position Do not rot...

Page 41: ...ection 6 of this manual When faults occur contact the Authorized Mitsubishi Service Representative or call Mitsubishi at 1 800 887 7830 Note The error code indicated on the FAULT DISPLAY Screen of the...

Page 42: ...he average ambient operating temperature Battery end of life is defined as the state of charge resulting in an ampere hour capacity less than or equal to 80 of nominal capacity Replace battery if capa...

Page 43: ...codes their description and required action At time of error A Verify and record the occurrence of the alarm Note fault code on the FAULT DISPLAY Screen of the LCD Display Contact Mitsubishi Electric...

Page 44: ...ge out of range Check AC input voltage 1 Alarm 22 AC input phase rotation error Check AC input voltage 1 Minor Flicker 23 Converter overload Call service engineer 1 Alarm Flicker 24 Converter over cur...

Page 45: ...58 Control circuit error Call service engineer 1 Minor Flicker 59 Control circuit error Call service engineer 2 Major Lit up 71 Overload Reduce load 1 Alarm Flicker 72 kW overload Reduce load 1 Alarm...

Page 46: ...ure UPS continues to operate normally but cause of alarm must be identified Over is defined as an overload condition Load will transfer from inverter to the static bypass line and may or may not retur...

Page 47: ...ter your UPS for warranty purposes please complete the warranty registration form and fax it to the Mitsubishi Electric UPS Systems Group Service Department fax line shown on the registration form Nex...

Page 48: ...nown Signature Date Which ONE of These Best Describes Your Organization s Number of Employees at This Location is Primary Business Classification Energy Producer __ Education Univ Service __ 1 19 __ 1...

Reviews: