Tag Addresses 2408
f & 2404f PROFIBUS Communications Handbook
8-2 2408
f & 2404f PROFIBUS Communications Handbook
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
Program Logic Status
162
BIT
DESCRIPTION
0
Program Output 1 ( 0 = OFF 1 = ON )
1
Program Output 2 ( 0 = OFF 1 = ON )
2
Program Output 3 ( 0 = OFF 1 = ON )
3
Program Output 4 ( 0 = OFF 1 = ON )
4
Program Output 5 ( 0 = OFF 1 = ON )
5
Program Output 6 ( 0 = OFF 1 = ON )
6
Program Output 7 ( 0 = OFF 1 = ON )
7
Program Output 8 ( 0 = OFF 1 = ON )
8
Reserved
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
Digital Output Status Word
551
BIT
DESCRIPTION
0
H Interface module telemetry (0 = Off, 1 = On)
1
J Interface module telemetry (0 = Off, 1 = On)
2
1A module telemetry (0 = Off, 1 = On)
3
LB logic telemetry (0 = Off, 1 = On)
4
LA logic telemetry (0 = Off, 1 = On)
5
1B module telemetry (0 = Off, 1 = On)
6
1C module telemetry (0 = Off, 1 = On)
7
2A module telemetry (0 = Off, 1 = On)
8
2B module telemetry (0 = Off, 1 = On)
9
2C module telemetry (0 = Off, 1 = On)
10
3A module telemetry (0 = Off, 1 = On)
11
3B module telemetry (0 = Off, 1 = On)
12
3C module telemetry (0 = Off, 1 = On)
13
AA relay telemetry (0 = Off, 1 = On)
14
Reserved
15
Reserved
Digital Input Status Word
87
BIT
DESCRIPTION
0
H Interface module (0 = Off, 1 = On)
1
J Interface module (0 = Off, 1 = On)
2
1A module (0 = Off, 1 = On)
3
LB logic input (0 = Off, 1 = On)
4
LA logic input (0 = Off, 1 = On)
5
1B module telemetry (0 = Off, 1 = On)
6
1C module (0 = Off, 1 = On)
7
2A module (0 = Off, 1 = On)
8
2B module (0 = Off, 1 = On)
9
2C module (0 = Off, 1 = On)
10
3A module (0 = Off, 1 = On)
11
3B module (0 = Off, 1 = On)
12
3C module (0 = Off, 1 = On)
13
Reserved
14
Reserved
15
Reserved
Parameter Description
Tag
Address
SP Rate Limit Holdback Status
0: Inactive
1: Active
41
Pot Break
350
Freeze Control Flag
0: Controlling
1: Hold
257
SP Rate Limit Active Status
0: No setpoint rate limit
1: Setpoint rate limit active
275
Sensor Break Status Flag
0: Good
1: Sensor break
258
Power Failed flag
0: Good
1: Power fail detected
259
New Alarm Flag
260
Loop Break Status Flag
0: Good
1: Loop break
263
Integral Hold Status Flag
0: Good
1: Integral hold
264
SRL Complete Status
0: Setpoint rate limit incomplete
1: Setpoint rate limit complete
277
Remote Input Status Flag
0: Good
1: Fault
280
Sync Continue Flag
0: Continue
1: Awaiting synch
281