background image

 3. Name of Each Part 

A1S62TCTT-S2

NC

NC

NC

NC

NC

NC

NC

NC

+

L2C

L2H

L1C

L1H

CH1

H OUT 
C OUT 
  ALM

RUN

H OUT 
C OUT 
  ALM

CH2

A1S62TCTT-S2

A1S62TCTTBW-S2

CH1

H OUT 
C OUT 
  ALM 

BR.W

RUN

CH2

H OUT 
C OUT 
  ALM 

BR.W

A1S62TCTTBW-S2



1


J



2

NC

NC

NC

NC

NC

NC

NC

NC

L2C

L2H

L1C

L1H



1


J



2

1)

1) 

2) 

2) 

3)

2

4

6

8

10

12

14

16

18

20

1

3

5

7

9

11

13

15

17

19

2

4

6

8

10

12

14

16

18

20

1

3

5

7

9

11

13

15

17

19

A1S62TCTT-S2  LED

A1S62TCTTBW-S2  LED

A

1S62TCTT-S2

CH1

H OUT 
C OUT 
  ALM

RUN

H OUT 
C OUT 
  ALM

CH2

A

1S62TCTTBW-S2

CH1

H OUT 
C OUT 
  ALM 

BR.W

RUN

CH2

H OUT 
C OUT 
  ALM 

BR.W

Number

Name

Description

RUN

A1S62TC operation status display

ON: Normal operation in progress
Flashing (2 sec. ON/2 sec. OFF): Write data error
Flashing (1 sec. ON/1 sec. OFF): Hardware error
OFF: 5V power shutoff, Watchdog timer error

OUT

Transistor output status display

ON: Transistor output ON
OFF: Transistor output OFF

ALM

Alert alarm status display

ON: Alert alarm is ON.
Flashing: The measured temperature range is

exceeded.

The thermocouple is not connected.
The thermocouple cable is

disconnected.

OFF: Alert alarm is OFF

1)

LED

BR.W

Heater wire breakage detection status display

ON: Heater wire breakage is detected.
OFF: Heater wire breakage is not detected.

2)

Cold junction
temperature
compensation
resister

Shipped with terminal block.

3)

Wire
breakage
detection
connector

Connector for current sensor

Wire breakage detection connevtor
instasllation screw

Cable fixing screw

BW1(For CH1)

BW2(For CH2)

NC(Unusable)

 4. Loading and Installation 

Precautions when handling the A1S62TC and installation environment
are explained.
For details of implementing and setting up this unit, please refer to the
User’s Manual for the PC CPU used.

4.1  Handling Instructions

1) The module case is made of plastic.  Be sure not to drop it or

subject it to strong vibration.

2) Do not remove the module printed circuit boards from the case.  It

may cause trouble.

3) When connecting the wiring, do not allow wire cuttings or other

foreign matter to enter from the top of the module.  Remove any
foreign matter from the module.

4) Tighten the module installation screws within the following

tightening torque range.

Screw position

Tightening torque range

Module installation screw (M4 screw)

78 to 118N

cm

Terminal block terminal screw (M3.5 screw)

59 to 88N

cm

Terminal block installation screw (M4 screw)

78 to 118N

cm

Wire breakage detection connector installation
screw (M2.6 screws)*

15 to 30N

cm

Cable fixing screw (M2 screws)*

11 to 14N

cm

*: Use only for A1S62TCTTBW-S2 .

4.2  Installations Enviroment

Never install the AnS series PC system in the following environments:
1) Locations where the ambient temperature is outside the range of 0

to 55

.

2) Locations where the ambient humidity is outside the range of 10 to

90%RH.

3) Locations where dew condensation takes place due to sudden

temperature changes.

4) Locations where there are corrosive and/or combustible gasses.
5) Locations where there is a high level of conductive power (such as

dust and iron filings, oil mist, salt, and organic solvents).

6) Locations exposed to the direct rays of the sun.
7) Locations where strong power and magnetic fields are generated.
8) Locations where vibration and shock are directly transmitted to the

main module.

 5. Wiring 

The precaution when wiring and the module connection example are
shown below.

5.1  Precaution when wiring

In order to have the best result from the A1S62TC functions and to
make the system highly reliable, an external cabling with low noise
effects are necessary.
The external wiring precautions are shown below:
1) Use separate cables for the alternating current and A1S62TC

external input signals to avoid A/C surges and induction effects.

2) Do not bunch the cables with the main circuit, high-voltage cable or

load cables from other than PC, or install them close to each other.
Install the cables far apart from high-frequency circuits, such as the
high-voltage cable and inverter load main circuit, as much as
possible.
This increases the noises, surges, and induction.

3) Perform a one-point grounding for the shielded line and shields of

the seal and cable at the PC.  However, there may be cases when
grounding should be performed externally depending on the noise
condition.

Summary of Contents for A1S62TCTT-S2

Page 1: ...ype III or above Not doing so could result in malfunction z When wiring in the PC be sure that it is done correctly by checking the product s rated voltage and the terminal layout Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or failure z Tighten the terminal screws with specified torque Loose terminal screws may cause a short ci...

Page 2: ...A CTL 6 P H 0 00 to 20 00A Former model CTL 6 P is also applicable Input method Multiplex method A D conversion Heater wire breakage disconnection specification Number of alert delays 3 to 255 I O occupied points Special 32 points Connection terminal 20 points terminal block Supported cable size mm inch 0 75 to 1 5 0 030 to 0 059 Supported solder less terminal R1 25 3 1 25 YS3 RAV1 25 3 V1 25 YS3A...

Page 3: ...op of the module Remove any foreign matter from the module 4 Tighten the module installation screws within the following tightening torque range Screw position Tightening torque range Module installation screw M4 screw 78 to 118N cm Terminal block terminal screw M3 5 screw 59 to 88N cm Terminal block installation screw M4 screw 78 to 118N cm Wire breakage detection connector installation screw M2 ...

Page 4: ... Rep Com e Assessoria Tecnica Ltda Av Rio Branco 123 15 and S 1507 Rio de Janeiro RJ CEP 20040 005 Brazil Tel 55 21 221 8343 Germany Mitsubishi Electric Europe B V German Branch Gothaer Strasse 8 D 40880 Ratingen GERMANY Tel 49 2102 486 0 U K Mitsubishi Electric Europe B V UK Branch Travellers Lane Hatfield Herts AL10 8XB UK Tel 44 1707 276100 Italy Mitsubishi Electric Europe B V Italian Branch Ce...