5 - 29
MELSEC-A
5 DATA USED FOR POSITIONING CONTROL
1) The backlash compensation is valid after completed the machine zero point
return. Thus, if the backlash compensation amount is set or changed, always
carry out machine zero point return once.
2) The backlash compensation amount setting range is 0 to 65535, but it should
be set to 255 or less by using the following expression.
Backlash compensation amount
0
≤
Movement amount per pulse
≤
255
[Table 1]
Pr.1
setting value
Value set with peripheral device
(unit)
Value set with sequence program
(unit) *
0 : mm
0 to 6553.5 (
µ
m)
0 to 65535 (
×
10
-1
µ
m)
1 : inch
0 to 0.65535 (inch)
0 to 65535 (
×
10
-5
inch)
2 : degree
0 to 0.65535 (degree)
0 to 65535 (
×
10
-5
degree)
3 : pulse
0 to 65535 (pulse)
0 to 65535 (pulse)
* 1 to 32767
: Set as a decimal
32768 to 65535 : Convert into hexadecimal and set
[Table 2]
Pr.1
setting value
Value set with peripheral device
(unit)
Value set with sequence program
(unit)
0 : mm
–214748364.8 to 214748364.7 (
µ
m) –2147483648 to 2147483647 (
×
10
-1
µ
m)
1 : inch
–21474.83648 to 21474.83647(inch) –2147483648 to 2147483647 (
×
10
-5
inch)
2 : degree 0 to 359.99999 (degree)
0 to 35999999 (
×
10
-5
degree)
3 : pulse
–2147483648 to 2147483647(pulse) –2147483648 to 2147483647 (pulse)
Pr.13 Software stroke limit upper limit value
Set the upper limit for the machine's movement range during positioning control.
Pr.14 Software stroke limit lower limit value
Set the lower limit for the machine's movement range during positioning control.
Software stroke
limit lower limit
Software stroke
limit upper limit
Zero point
(Machine movement range)
Emergency stop
limit switch
Emergency stop
limit switch
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......